Manuel d'installation / Installation guide IMEON Inverter/ Guia de montaje – Rev C.12
IMEON INVERTER
Software service failure. Please reboot the inverter. Please reboot the inverter and check the
version is the last one. If the problem remains, please contact your distributor.
PV overvoltage. This problem may cause a critical electronic damage, stop immediately the
PV production and check the PV sizing and installation. If the problem remains, please
contact your distributor.
PV overcurrent. This problem may cause a critical electronic damage, stop immediately the
PV production and check the PV sizing and installation. If the problem remains, please
contact your distributor.
Solar insulation too low. Measure the PV insulation which must be higher than 600kOhm for
IMEON 3.6 and 1Mohm for IMEON 9.12. If the problem remains, please contact your
distributor.
DC BUS overvoltage. This problem may cause a critical electronic damage. Please reboot
the batteries and the inverter. If the problem remains, please contact your distributor.
DC BUS undervoltage. Please reboot the inverter, activate the AC BACKUP and connect the
battery. If the problem remains, please contact your distributor.
DC BUS soft start timeout. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
Inverter circuit soft start timeout. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
Inverter overcurrent. Inverter may have a critical failure as a result of an overload or a short
circuit. Stop immediately the inverter and check the installation. If the problem remains,
please contact your distributor.
Overheating. This problem may cause a critical electronic damage, stop the inverter and
check the good ventilation of inverter and temperature of the room.
Internal relay failure. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
DC current sensor failure. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
PV overvoltage. This problem may cause a critical electronic damage, stop immediately the
PV production and check the PV sizing and installation. If the problem remains, please
contact your distributor.
Over leakage current. Check that all the devices connected to the installation are wired on a
unique ground system. If the problem remains, please contact your distributor.
DC BUS overcurrent. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
CPU1 measurement error. Please reboot the inverter and check the version is the last one. If
the problem remains, please contact your distributor.
GFCI sensor failure. Please reboot the inverter. If the problem remains, please contact your
distributor.
AC input ground lost. There is an electrical security problem. Please check the inverter earth
connection.
Discharge DC BUS failure. This problem may cause a critical electronic damage. Stop
immediately the inverter and check the installation. If the problem remains, please contact
your distributor.
Discharge DC BUS soft start timeout. This problem may cause a critical electronic damage.
Stop immediately the inverter and check the installation. If the problem remains, please
contact your distributor.
Overload on the AC BACKUP. Remove the high power devices with inrush power. If the
problem remains, please contact your distributor.
Overcurrent on the AC BACKUP. Remove the high power devices with inrush power. If the
problem remains, please contact your distributor.
Description