IMEON INVERTER
Step 2: Make sure the wires are securely connected.
Step 3: Plug the RST connector in the GRID CONNECTION socket.

3.10 AC BACKUP connection

WARNING: It is very important for the safety and efficiency of
the system to use the appropriate AC connection cables.
WARNING: Please use maximal protection according to the existing standards (circuit breaker,
differential current breaker). The circuit breaker must protect against currents exceeding the
maximum output current of the inverter (17 A per phase). Use a circuit breaker Type A 30mA.
Note: The inverter current (battery + PV) cannot exceed 13A nominal per phase. In the case of grid
outage, make sure not to go over this figure.
Note: In case of the operation with PV only (grid outage and no battery), the AC BACKUP of the
inverter will not be activated.
Note: To prevent further supply to the load via the inverters AC BACKUP during any mode of
operation, an additional disconnection device should be placed in the buildings wiring
installation.
Step 1: Open the circuit breaker in order to work safely on the installation.
Step 2: Remove insulation sleeve and connect wires according to polarities indicated on the terminal
block. Be sure to connect PE protective conductor (
Manuel d'installation / Installation guide IMEON Inverter/ Guia de montaje – Rev C.12
) first.