Set the outlet side at a right angle to the direction of the wind.
Strong wind
Blown air
3
Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
4
If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 5.9 inch (150 mm)).
5
If you install the unit on a frame, please install a waterproof plate
within 5.9 inch (150 mm) of the underside of the unit in order to
prevent the invasion of water from the lower direction.
6
When installing the unit in a place frequently exposed to snow,
pay special attention to elevate the foundation as high as
possible.
7
If you install the unit on a building frame,
please install a waterproof plate (field
supply) (within 5.9 inch (150 mm) of the
underside of the unit) or use a drain kit in
order to avoid the drainwater dripping.
(See figure).

Selecting a location in cold climates

NOTE
When operating the outdoor unit in a low outdoor
ambient temperature, be sure to follow the instructions
described below.
To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
To prevent exposure to wind, install a baffle plate on the air
discharge side of the outdoor unit.
In heavy snowfall areas it is very important to select an
installation site where the snow will not affect the unit. If lateral
snowfall is possible, make sure that the heat exchanger coil is
not affected by the snow (if necessary construct a lateral
canopy).
1
2
Installation manual
4
Strong wind
1
Construct a large canopy.
2
Construct a pedestal.
Install the unit high enough off
the ground to prevent burying in
snow.
P
RECAUTIONS ON INSTALLATION
Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.
In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of 1/2 inch (M12) foundation bolts, nuts and washers each
which are available on the market.)
It is best to screw in the foundation bolts until their length are
0.79 inch (20 mm) from the foundation surface.
(inch)
A
5.51
24.41
B
1.85
16.65
24.17
(mm)
A
140
620
B
47
423
614
A
Discharge side
B
Bottom view
C
Drain hole

Drain work

Make sure the drain works properly.
Draining of the outdoor unit is field supply.
Drain holes may not be made smaller with a build up of ice on
the bottom plate as a possible result.
NOTE
If drain holes of the outdoor unit
are covered by a mounting base
or by floor surface, raise the unit
in order to provide a free space
of more than 4 inch (100 mm)
under the outdoor unit.
5.51
C
140
C
ERLQ036~054BAVJU
Outdoor unit for air to water heat pump
4PW55905-1