Transmitter
Actual value alarm A1
Alarm threshold
120 ppm
Hysteresis
5 ppm
Actual value alarm A2
Alarm threshold
120 ppm
Hysteresis
5 ppm
Actual value alarm A3
Alarm threshold
120 ppm
Hysteresis
5 ppm
Actual value alarm A4
Alarm threshold
120 ppm
Hysteresis
5 ppm
Mean value alarm A1
Alarm threshold
20 ppm
Hysteresis
4 ppm
Mean value alarm A2
Alarm threshold
40 ppm
Hysteresis
8 ppm
Mean value alarm A3
Alarm threshold
60 ppm
Hysteresis
10 ppm
Mean value alarm A4
Alarm threshold
60 ppm
Hysteresis
10 ppm
Hysteresis of e.g. 10 ppm with a limit of e.g. 100 ppm means that the alarm is set at 100 ppm and reset if the value falls below 90 ppm.
1)
Presetting according to VDI 2053 (2004)
Dräger VarioGard
CO
NH
3
1)
Transmitter
Transmitter
50 ppm
20 % by vol.
5 ppm
0.2 % by vol.
200 ppm
19 % by vol.
20 ppm
0.2 % by vol.
500 ppm
18 % by vol.
50 ppm
0.2 % by vol.
1000 ppm
17 % by vol.
100 ppm
0.2 % by vol.
1200 ppm
0 ppm
1200 ppm
0 ppm
1200 ppm
0 ppm
1200 ppm
0 ppm
O
NO
2
Transmitter
10 ppm
3 ppm
15 ppm
3 ppm
20 ppm
3 ppm
20 ppm
3 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
0 % by vol.
50 ppm
0 % by vol.
5 ppm
NO
CH
2
4
Transmitter
Transmitter
1 ppm
10 %UEG
0.1 ppm
5 %UEG
2 ppm
20 %UEG
0.2 ppm
5 %UEG
3 ppm
40 %UEG
0.3 ppm
5 %UEG
5 ppm
40 %UEG
0.5 ppm
5 %UEG
1 ppm
40 %UEG
0.1 ppm
3 %UEG
2 ppm
80 %UEG
0.2 ppm
3 %UEG
3 ppm
100 %UEG
0.3 ppm
3 %UEG
5 ppm
100 %UEG
0.5 ppm
3 %UEG
Configuration
LPG
Transmitter
10 %UEG
5 %UEG
20 %UEG
5 %UEG
40 %UEG
5 %UEG
40 %UEG
5 %UEG
40 %UEG
3 %UEG
80 %UEG
3 %UEG
100 %UEG
3 %UEG
100 %UEG
3 %UEG