Descargar Imprimir esta página

System Sensor WSF-RF Serie Instrucciones De Instalación página 2

Sirena de montaje en pared del sistema de radio

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Figure 4: Battery Installation and Rotary Address Switches
+
+
ROTARY
ADDRESS
SWITCHES
4a
4c
Honeywell Products and Solutions Sàrl
(Trading as System Sensor Europe)
0905 20
DOP-IRF032
EN 54-25: 2008 / AC: 2010 / AC: 2012
WSF-[xx]-RF
[xx] =
RR Red
WR White
EN 54-23: 2010 - Fire Alarm Devices: Visual Alarm Devices
(Red Strobe)
X
D200-311-00
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
1
2
+
3
4
+
4b
4d
Zone d'activités La Pièce 16
CH-1180 ROLLE, Switzerland
- Components Using Radio Links
EN 54-3: 2001 & 2014+A1
- Fire Alarm Devices: Sounder
Y
Do not mix batteries from different manufacturers. When changing
Using these battery products for long periods at
temperatures below -20°C can reduce the battery
SETTING THE ADDRESS
+
Set the loop address by turning the two rotary decade switches on the
underside of the sounder strobe (see figure 4), using a screwdriver to rotate
the wheels to the desired address.
Except when Advanced Protocol (AP) is being used (see below) the
NOTE
sounder strobe will take two module addresses on the loop; the sounder
POLARITY
address will be the number shown on the switches (N), the strobe address
will be incremented by one (N+1). So for a panel with 99 addresses, select
a number between 01 and 98.
In Advanced Protocol (AP) addresses in the range 01-159 are available.
Depending on panel capability, only one loop address is required if using
sub-addressing for the sounder and strobe functions, (check the panel
documentation for information on this).
Set the loop address on the sounder strobe module Before
PROGRAMMING
Configuring the Sounder Settings
Volume setting
The sounder has 3 possible volume settings: Low, Medium, High.
The sounder is supplied configured with the volume set to HIGH (factory
default setting). To change the volume to a different setting requires a
separate programming operation using the Device Direct Command in
AgileIQ (See Radio Programming and Commissioning Manual - ref. D200-
306-00 for details.)
1) Take the un-commissioned sounder strobe, ensure that the address is
set to 00 (default setting).
2) Insert the batteries.
3) Select the Device Direct Command tab in AgileIQ, double click on the
screen to reveal the options and follow the instructions to configure the
sounder volume setting.
It is recommended that the sounder's output volume configuration is noted
for future reference on the sounder label after programming:
OUTPUT VOLUME: High __ Medium __ Low __
Tone setting
The sounder is supplied configured with the tone setting 8 (factory default
setting), with the second stage tone as 2 (see tone table). To change the
tone to a different setting requires a separate programming operation using
the Device Direct Command in AgileIQ (See Radio Programming and
Commissioning Manual - ref. D200-306-00 for details.)
1) Take the un-commissioned sounder strobe, ensure that the address is
set to 00 (default setting).
2) Insert the batteries.
3) Select the Device Direct Command tab in AgileIQ, double click on the
screen to reveal the options and follow the instructions to configure the
sounder tone settings.
It is recommended that the sounder's tone configuration is noted for future
reference on the sounder label after programming:
1st STAGE TONE No: __ 2nd STAGE TONE No: __
Note: Remove the batteries from the device after setting the tone/
volume or strobe functions if the system commissioning operation is
not about to be done.
Commissioning
1) Ensure that the correct address has been set on the device.
2) Insert the batteries.
3) Fit the sounder strobe in its base (as shown in Figure 2).
Z
To load network parameters into the RF sounder strobe, it is necessary to
link the RF gateway and the RF sounder strobe in a configuration operation.
At commissioning time, with the RF network devices powered on, the RF
gateway will connect and programme the sounder strobe and all the other
RF devices in the system with the necessary network information. The RF
sounder strobe then synchronises with its other associated devices as the
the batteries, all 4 will need to be replaced.
life considerably (by up to 30% or more)
Important
inserting the batteries
I56-6661-001

Publicidad

loading

Este manual también es adecuado para:

Wsf-rr-rfWsf-wr-rf