Descargar Imprimir esta página
Lutron PDT-T-DV-MF Instrucciones De Instalación
Lutron PDT-T-DV-MF Instrucciones De Instalación

Lutron PDT-T-DV-MF Instrucciones De Instalación

Kit de terminales para módulo din de alimentación eléctrica múltiple

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Enlaces rápidos

Multi-Feed DIN Module
Terminal Kit
PDT-T-DV-MF
100 / 120 / 277 V~ 80 A 50/60 Hz
Installation Instructions
Please Read Before Installing
P/N 043594 Rev. A
1. Turn power off to all feeds to the panel.
WARNING – Shock hazard. May result in Serious Injury or
Death. This may be fed by multiple circuits. Locate and lock
each supply breaker in the off position before proceeding.
2. Select module position and locate the terminal blocks
associated with that position. Modules may be placed in any
available mounting location in a Lutron DIN rail panel.
3. Install terminal kit. Components provided with PDT-T-DV-MF are
shown in Figure 2. To properly install the kit, first remove the pre-
installed bypass jumper from the red and black terminal blocks using
the removal tool provided with the panel (Figure 3a). Remove upper
end stop and labels from the dimmed line / hot (red) terminal blocks.
The line / hot label will need to be broken from the strip and replaced
(Figure 3b). Move the neutral terminal blocks (white) and separate the
dimmed line / hot terminal blocks (Figure 3c). Install the provided kit
as shown in Figure 4. Ensure the bypass jumper barrier in center of
terminal block is oriented toward the bottom of the panel
4. Install the wiring harness. Use the PDW-T-DV-MF (sold separately)
to wire the multi-feed DIN module (Figure 5).
5. Mount the multi-feed DIN module into the DIN rail panel.
The multi-feed DIN module will snap onto the DIN rail.
6. Connect the module to the QS link. If using a Lutron harness,
follow instructions provided with QS harness.
7. Connect the load and line wires to the left side of the terminal
blocks as shown. Do not overtighten screws. Torque to 5.31 in-lb to
7.08 in-lb (0.60 N•m to 0.80 N•m).
8. Verify wiring safety.
WARNING - Shock hazard. May result in serious injury or
death. Only turn on input feed circuit breakers when load
wiring is complete and it is safe to have power applied.
9. Test all load wiring. Turn on input power to the module locations.
Check all connected loads. If a circuit breaker trips, a wiring error exists
and must be resolved.
10. Refer to the DIN panel instruction sheet to complete panel
installation.
Warranty: For warranty information, please see the warranty enclosed with the product,
or visit www.lutron.com/TechnicalDocumentLibrary/Intl_Warranty.pdf
The Lutron logo and Lutron are trademarks or registered trademarks of Lutron
Electronics Co., Inc. in the US and/or other countries.
©2024 Lutron Electronics Co., Inc.
Lutron Elec tron ics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299 USA
English
Figure 1
Figure 2
PDT-T-DV-MF Components
Pre-installed terminal block
configuration
End Stop
End Cap
N1
N1
1
N1
Neutral Terminal
1
Blocks (White)
N1
2
N1
Bypass
2
Jumper Barrier
DH1
3
DH2
Output Terminal
3
DH3
Blocks (Red)
4
DH4
4
Line Terminal
H1
Block (Black)
Labels
N/C
GND
Ground Terminal Block (Green / Yellow)
End Cap
End Stop
Figure 3
Extraction Tool
a.
b.
b.
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
DH1
DH1
DH2
DH2
Bypass
DH3
Jumper
DH3
DH4
DH4
H1
H1
N/C
GND
N/C
Figure 4
PDT-T-DV-MF Installation
c.
New End Stop
N1
N1
N1
N1
N1
N1
N1
N1
N1
N1
New Bypass
1
Jumpers (x4)
1
2
2
New Black
3
Terminal Blocks (x4)
3
4
4
New End Cap
New
H1
H1
Labels
N/C
GND
N/C
GND
Customer Assistance: U.S.A., Canada, and the Caribbean: 1.844.LUTRON1 | Mexico: +1.888.235.2910 | Europe: +44.(0)20.7680.4481 | Asia: +86.21.61650990 | Other Countries: +1.610.282.3800 | www.lutron.com
Need Help? www.lutron.com or call the Lutron
Terminal Configuration and Wiring
Figure 5 - Panel Configuration for QSN-4T20-D shown
End Stop
End Cap
Line Terminal
Blocks (Black)
Bypass
N1
Jumper (x4)
N1
N1
Control
N1
Neutral
Load
N1
1
Neutral
1
2
Line / Hot
2
3
3
4
Control
4
Hot
H1
N/C
GND
Customer Asstistance, at 1.844.LUTRON1 or +1.610.282.3800
GND

Publicidad

loading

Resumen de contenidos para Lutron PDT-T-DV-MF

  • Página 1 ©2024 Lutron Electronics Co., Inc. Lutron Elec tron ics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299 USA Customer Assistance: U.S.A., Canada, and the Caribbean: 1.844.LUTRON1 | Mexico: +1.888.235.2910 | Europe: +44.(0)20.7680.4481 | Asia: +86.21.61650990 | Other Countries: +1.610.282.3800 | www.lutron.com...
  • Página 2 étiquettes incluse avec le produit, ou consultez www.lutron.com/TechnicalDocumentLibrary/Intl_Warranty.pdf Le logo Lutron et Lutron sont des marques commerciales ou déposées de Lutron Electronics Co., Inc. aux États-Unis et/ou dans d’autres pays. ©2024 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299 É.-U.
  • Página 3 ©2024 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299 E.U.A. Asistencia al cliente: E.U.A., Canadá y el Caribe: 1.844.LUTRON1 | México: +1.888.235.2910 | Europa: +44.(0)20.7680.4481 | Asia: +86.21.61650990 | Demás países: +1.610.282.3800 | www.lutron.com...
  • Página 4 ©2024 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299 EUA Atendimento ao cliente: EUA, Canadá e Caribe: 1.844.LUTRON1 | México: +1.888.235.2910 | Brasil: +1.610.282.6701 | Europa: +44.(0)20.7680.4481 | Ásia: +86.21.61650990 | Outros países: +1.610.282.3800 | www.lutron.com...
  • Página 5 LutronロゴおよびLutronは、米国およびその他の国におけるLutron Electronics Co., Inc., の商標または登録商標です。 ©2024 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. | 7200 Suter Road | Coopersburg, PA 18036-1299 USA カスタマー ・ アシスタンス : 米国、 カナダ、 カリブ海地域 : 1.844.LUTRON1 | メキシコ:+1.888.235.2910 | ヨーロッパ:+44.(0)20.7680.4481 | アジア:+86.21.61650990 | その他の国:+1.610.282.3800 | www.lutron.com...