3.
TECHNICAL
SPECIFICATIONS
MODEL
Nominal Voltage (V)
Current (A)
Power (W)
Cooling capacity (W)
Coefficient of performance
Refrigerant
Oil
Quantity of refrigerant (g)
Speed range (RPM)
Internal Dimensions (mm)
External dimensions (mm)
Power cable
Electrical box Green GT30s 24V - DS600031
18
Electrical box Green GT30 12V - DS600030
DS600030
DS600031
12
24
40-60
21-42
500-800
350-1000
1800
2400-3000
≥ 2,4
≥ 2,6
R134a
ISO VG68 (110ml)
560± 5g
1000 - 3000
400 X 243 X 150
950 X 730 X 165
Ø16mm x 7m
Ø8mm x 7m
4.
ERROR CODE ON THE
INTERNAL PANEL
(EVAPORATOR UNIT)
•
The product may fail if the codes below appear
on the display while the air-conditioner is
in use. To correct the fails, reduce the air
conditioner's speed and turn it off after 10
minutes. Turn it back on. If the codes persist,
turn off the system and contact a specialized
technician. If the code disappears, continue
to use the part.
•
Error codes:
E01
-
Low voltage - Low battery charge;
-
E02
Probable bad contact of the Box Motor -
check cables, connectors and/or the need to
replace the ventilation motor
-
E04
Pipe (outgoing air) temperature sensor;
-
E05
Compressor is overheating - as soon
as the Compressor returns to a normal
temperature, it will start again automatically;
-
E06
Check whether the circuit leading from
the Compressor to the Condenser Electrofan
is open;
E07
-
Check possible short circuit between
compressor and condenser fan;
E09
-
Problem on the electric fan control
board - replace the board;
-
E10
Replace the condenser fan;
ATTENTION:
IF THE "ON ALERT" CODE ON THE COMPRESSOR'S FAULT
INDICATOR DOES NOT CORRESPOND TO THE CODES DESCRIBED IN THE
TABLE ABOVE, REPLACE THE COMPRESSOR CONTROL BOARD.
Electrical box Green GT30s 24V - DS600031
Electrical box Green GT30 12V - DS600030
ENGLISH
E11
-
Check for possible damage to the
cables connecting the compressor to the
condenser fan.
-
H22
Air entrance sensor failure indicates
that the mode can be changed after
returning to normal;
-
H23
Air Outlet Sensor fault indicates that
the mode can be changed after returning
to normal;
19
19