The compressor runs for
a long time but doesn't
cool properly (reduced
efficiency).
The fuse blows.
The
compressor
is
operating intermittently.
The compressor never
stops
(correct
fridge
performance)
The compressor never
stops
(poor
fridge
performance)
For more complicated defects requiring specialised assistance, please contact Indel B S.r.l. Italia or your nearest TL 16 retailer.
ONLY FOR SALES WITHIN THE
EUROPEAN COMMUNITY (EU)
This appliance is marked according to the European Directive 2012/19 / EU (WEEE). The symbol on the
product indicates that this product should not be treated as household waste.
Ensure that this product is not entered as part of the flows of municipal waste but treated as professional
WEEE.
33
Insufficient
ventilation,
the condensation unit is
overheating. The fan is not
working properly. There is too
much frost on the evaporator.
The door does not close
properly and lets in warm,
moist air. The condenser is
blocked by dust.
The wrong fuse is being used.
Defective electronic control
unit.
Battery low or electrical
cables in poor conditions.
Incorrect
thermostat
connection on the electronic
control
unit.
Thermostat
broken. Condensation is not
working properly, evaporator
cools but not enough to cause
the thermostat to stop the
compressor.
Environment very hot +
insufficient ventilation or little
gas in the refrigerant circuit.
OFF IS A BRAND OF INDELB
Increase the ventilation. Replace the fan. Defrost the unit.
Correct the position of the door and check the gasket.
Clean the condensing unit.
Check the fuse. Replace the electronic control unit.
Check wiring conditions, examining for loose connections,
rust or verdigris. If wiring needs to be replaced, see the
manual for correct sizing. If wiring is in good conditions,
check battery function and replace if in poor condition.
Rotate the thermostat to off position. If the refrigerator
continues to function, then there is continuity on the control
unit. Correct the problem on thermostat connections (make
sure the bridge is present on C and P and not on C and T
on the electronic control unit). Rotate the thermostat to off
position. If the compressor switches off but it is impossible
to regulate temperature, replace the thermostat or recharge
the cooling system.
Check ventilation. The compressor must be installed in a
well-ventilated location. If possible, remove the refrigerator
from the installation hole. If the refrigerator operates better,
improve ventilation, consulting the manual for correct
installation. If ventilation is instead optimal, check for the
presence of gas in the system, contacting a specialised
technician.