Register Discrete input
10009
SW8
10010
Alarm
Input registers (Read)
Register Discrete input
30001
SetPoint
30002
SetPoint Value
Light guide
30003
intensity
30004
Analog Output
30005
IAQ sensor TVOC
30006
IAQ sensor CO2
30007
Temp sensor
30008
Hum sensor
30009
CO2 sensor
30010
Working mode
30019
Airsens version
Data type Range
0 : OFF
BIT
1 : ON
0 : OFF
BIT
1 : ON
Data type Range
16bits
0-100
16bits
0-2000
16bits
0-100
16bits
0-100
16bits
0-500
16bits
450-2000
16bits
-100-500
16bits
0-100
16bits
450-2000
1 : MF1
2 : MF2
16bits
3 : MF3
4 : MF4
16bits
1-8
Default Comments
-
No function
Error: Defective sensor,
communication fault or other
-
problem
OFF: Working correctly
ON: Alarm
Default Comments
-
P1 potentiometer position (%)
P1 potentiometer value (ppm
-
or HR)
-
P2 potentiometer position (%)
Analogue output (Vdc)
-
(Example: 56 = 5,6Vdc)
-
VOC index
VOC sensor equivalent value
-
(ppm)
Temperature sensor value (°C)
-
(Example: 213 = 21,3°C)
-
Humidity sensor value (%HR)
-
CO2 sensor value (ppm)
-
Operating mode
1 : AIRSENS RH
-
4 : AIRSENS VOC
6 : AIRSENS CO2
55