Installation and network integration of a CS141
1. Initial configuration
On delivery, the IP address is 10.10.10.10 and the CS141 is in
manual mode. As soon as you assign an IP address, the CS141
will take over the new settings without reboot:
1. Leave the sliding switch in the left position.
2. Connect the CS141 to the LAN port of your workstation via,
either directly or via a switch.
When the IP address is wrong, it is possible to fall back to the
hard coded IP address 10.10.10.10 by setting the sliding switch to
center position and rebooting the device.
2. Connecting the UPS
... when using an external CS141
Use the original serial cable to connect COM port 1 of the CS141
to the RS232 interface of the UPS.
... when using a CS141 Slot card
Insert the CS141 diectly into the according card slot of the UPS.
You do not need to switch off the UPS.
3. Powering up the CS141
... when using an external CS141
Connect the power adapter coming with the CS141 device. As
soon as power is available, the CS141 will start booting.
... when using a CS141 slot card
The CS141 slot card will be powered by the internal connectors of
the slot provided by your UPS. As soon as you plug in the slot
card, it will power up and start booting.
4. Computer Setup and First Access
Windows Operating System
4.1. Add a route to your local computer
1. Run the windows build-in command prompt with the option
„run as administrator" via the windows context menu.
2. Enter the following command:
route add 10.10.10.10 <local IP address>
(Example: "route add 10.10.10.10 192.168.1.54")
3. Windows will give the feedback „OK".
4.2. Access the CS141 via HTTP
1. Open a common web browser.
2. Enter „http://10.10.10.10"
3. Enter the default access data:
Name:
admin
Password:
cs141-snmp
Initial IP address: 10.10.10.10
Ethernet
Cable
Slider to left position
Switch
Hard coded IP address 10.10.10.10:
Slider to CENTER position
External CS141
Connect the UPS via RS232 / RS485
Slot card
External CS 141: connect power adapter
EU: 230V AC / 12V DC
US: 120V AC / 12V DC
Insert card
into the slot