UV Installation Location
The power module must be mounted directly to a metal surface.
This will help the ballast dissipate heat. Failing to mount the ballast properly will void warranty and may
lead to premature UV lamp failure.
This device may be installed in an air handler unit, a
cased evaporator coil, or in an air plenum/duct.
If the UV device is installed on the inlet side (return air side)
of a coil, make sure that the UV rays are directed away from
any filter medias, plastic duct lining, plastic components, or
accessible doors and panels. When properly installed, the
UV lamp shield included in your package may help divert
stray UV away from undesired directions.
If the UVC lamp is placed inside of a cased system, the
included magnetic switch is required to be attached to the
access panel(s) of the system.
If the UV device is installed near an air filter, check with
filter manufacturer for UV-C resistance properties. Optional
UV directional lamp shield is included. See page 2.
If the desired UV installation location is intended to irra-
diate an air filter, to neutralize the microbiological matter
on the air filter surface, such as would be found in the
return air drop of a basement application or in the return
plenum of a horizontal system in an attic; take precautions
as described in note above, and make sure the UV fixture
is placed on the return side of the filter. DO NOT INSTALL
THE UV FIXTURE ON EITHER SIDE OF THE FILTER IN
HALL / CLOSET RETURN AIR APPLICATIONS.
WARNING: UV Light Hazard.
Can cause serious eye and skin damage.
Harmful to bare skin and eyes. Can cause temporary
or permanent loss of vision. Never look at lamps while
illuminated.
Remote Lamp Installation (A-Coil Delta Plate)
Note: Open the access panel to the A-coil. Drill
•
a 7/8" knockout into the delta plate and place
gasket (included) around knockout.
(Optional) Attach UV lamp shield to direct UV
•
away from furnace access panels. See page 2.
Insert lamp directly into knockout and secure
•
the lamp to the delta plate with two self-drilling
screws. (Screws and rubber washers included.)
Connect remote lamp extension cord. Note:
•
A-Coil delta plate installation does not use
lamp bracket.
Cased evaporator coil/furnace
Fig. 3.
Air handler installation.
Fig. 4.
Insert lamp into delta plate knockout and
Fig. 5.
secure with screws and washers. Connect
remote lamp extension cord.
4
Duct
Magnetic
Switch
Power Module
To 24V
Step Down
Transformer
(not included)
installation.
To 24V
Step Down
Transformer
(Not included)
Magnetic
Switch
Power Module
Remote Lamp
Extension Cord
UV-C Lamp