Descargar Imprimir esta página

Honeywell Home UV2400U2000 AirBRIGHT 2 Instrucciones De Instalación página 5

Purificador de aire ultravioleta

Publicidad

Idiomas disponibles

Idiomas disponibles

Power Module Installation (Remote Lamp)
With the lamp cordage facing away from the
mounting surface, install the power module in
a suitable location on the side of the system or
within the control panel of the air handler using
the two long self-drilling screws (included). Do
not overtighten.
Drill a 7/8" knockout in the outer sheet metal
where the remote lamp extension cord will be
inserted.
Connect the power module to constant 24 VAC
power.
Connect magnetic switch. See page 6.
Connect lamp to power module. Connectors are
keyed for proper alignment.
WARNING
UV Light Hazard.
Can cause serious eye and skin damage. Do not look at UV-C light. Harmful to bare skin and eyes. Can
cause temporary or permanent loss of vision. Never look at lamps while illuminated.
NOTICE
Clean lamp prior to installation.
Use a cotton cloth to remove dirt and fingerprints. Failure to do so could shorten the lamp's lifespan.
NOTICE
Fully Seat Lamp Connector.
Failure to properly seat lamp connector could result in improper lamp operation and/or compromise water
resistance.
NOTICE
Lamp cleaning not required after installation.
Reference specifications page for lamp replacement part number and schedule.
Direct Lamp Installation (A-Coil Delta Plate)
Drill a 7/8" knockout in the outer sheet metal
where the lamp will be centered on the return
side of the coil. See diagram.
Place gasket (included) around knockout.
Insert lamp into power module and secure with
self-drilling screws. (Included.)
(Optional) Attach UV lamp shield to direct UV
away from furnace access panels and critical
plastic components. See page 2.
Insert lamp directly into knockout and secure
power module to duct with self-drilling screws
(Included.) Note: A-Coil delta plate installation
does not use lamp bracket.
Secure power module to air handler or duct
Fig. 6.
with long screws. Do not overtighten.
Insert lamp into power module and
Fig. 7.
5
Magnetic
Switch
Remote Lamp
Extension Cord
Power Module
UV-C Lamp
To 24V
Step Down
Transformer
(Not included)
secure with screws.

Publicidad