Power Module Installation (Direct Lamp)
Drill a 7/8" knockout in the outer
sheet metal where the power cord and
magnetic switch signal wire will be
inserted.
Connect the power module to constant
24 VAC power.
Connect magnetic switch. See figure 11.
Connect lamp connector to power
module connector. Connectors are keyed
for proper alignment.
WARNING
Electric Shock Hazard.
Can cause injury or death.
Disconnect all electrical power supplies before
servicing.
WARNING
For Use With 24 VAC Only.
Do not exceed voltage rating.
Severe damage to device and/or fire could result.
Verify proper voltage.
Remote Lamp Installation (W-Coil / A-Coil Bracket Mount)
Disconnect power to the air handler and open
access panels.
Slit insulation on the back or side wall of air
handler and attach magnetic bracket to the
wall. Bracket may optionally be secured using
screws.
(Optional) In coil applications, use lamp shield
to direct UV away from furnace access panels.
See page 2.
Secure the lamp to the lamp bracket with the
provided knurled nuts.
Install power module in accordance with steps
defined on page 6.
Magnetic Switch Installation
To comply with UL Standards, a magnetic
switch must be deployed across all access
panels and doors that can expose an operator
to more than of 1.7 μW/cm2 UV intensity.
When possible, it is recommended to mount the
magnetic switch across two door panels.
Switch wires are not polarity-sensitive.
Max mounting gap: 5/8".
Remove interlock protective covers for access
to screw mounting holes. Replace protective
covers after mounting.
If installing the device in ducting with no
operator access, the magnetic switch can be
bypassed by wire-nutting the two signal wires
together.
Insert assembly into delta plate knock-
Fig. 8.
out and secure with screws.
Connect magnetic switch and power cord.
Fig. 9.
Attach lamp to lamp bracket and install in
Fig. 10.
Magnetic switch installation location.
Fig. 11.
6
Magnetic
Switch
Power Module
To 24V
Step Down
Transformer
(Not included)
desired location.