KCER-01MF
Multifunction Tester
1.4. Caution
Do not change functions on the test instrument with the test leads in place, i.e. changing from a "dead test" to
a test where the supply is required could damage the instrument.
1.5. Declaration of Conformity
This instrument has been tested according to the below regulations:
EN 61326: Electrical equipment for measurement, control and laboratory use.
EN 61010-1: Safety requirements for electrical equipment for measurement, control and laboratory use
– Part 1: General requirements.
BS EN61557: Electrical safety in low voltage distribution systems up to 1000V a.c. and 1500V d.c.
Equipment for testing, measuring or monitoring of protective measures.
Part 1 General requirements
Part 2 Insulation resistance
Part 3 Loop resistance
Part 4 Resistance of earth connection and equipotential bonding
Part 6 Residual current devices (RCDs) in TT and TN systems
Part 7 Phase sequence
Part 10 Combined measuring equipment
1.6. Error Codes
Various error conditions are detected by the tester and are indicated with the icon, "Err", and an error number
on the primary display. See Table 1. These error conditions disable testing and, if necessary, stop a running
test.
Table 1. Error Codes
Error Condition Code
Solution
Fault Voltage
Over Temp
Excessive Noise
Excessive Probe Resistance 4
Self Test Fails
4
Code
Solution
Check the installation, in particular, the
1
voltage between N and PE.
2
Wait while the tester cools down.
3
Switch off all appliances (Loop, RCD
measurements) and move the earth stakes
(earth measurement).
Put the stakes deeper into the soil. Tamp
down the soil directly around the stakes.
Pour water around the stakes but not at the
earth ground under test.
5
Return the tester to a Service Center.