KCER-01MF
Multifunction Tester
not be accurate due to "mains" interference - test to be repeated
5.1.3. Displayed icons (symbols) and messages in RCD function
test leads to the appropriate terminals.
If the wiring condition is other than normal, the Tester is limited on its measurements that can be performed.
Notes:
1) Will not detect two hot wires in a circuit.
2) Will not detect a combination of defects.
3) Will not detect reversal of grounded and grounding conductors.
:Indicates the battery status.
:80%~100%
:50%~80%
:20%~50%
:6%~20%
:Low Battery
:Indicates high temperature and therefore cannot make any measurements
Message:
Half : Appears during the auto test when rcd has operated on the x ½ test
Half Trip: Appears during the manual test when rcd has operated on the x ½ test
UL OVER :Appears when UF voltage exceeds the previously set UL voltage. (UL voltage can be set to 25V
or 50V) The user must check the impedance between L-PE
5.1.4. Displayed icons (symbols) and messages when using the LOW OHM and CONTINUITY
functions
Symbol:
: Low Battery (The icon will be flashing along with the beep sound).
: The resistance of the test leads are included in the test measurement
18
:Indicates the correct input terminal connectivity . The user should connect the
:Indicates L connection is connected on the N input terminal and vice-versa
:Indicates no connection on the PE input terminal
Indicates correct input terminal connectivity. The user should connect
: the test leads to the appropriate terminals indicated by color coding.