Multifunction Tester
2.Press TEST button if re-test is necessary.
When symbol from
,
,
appears lower left corner, and if the
voltage exceeds 260V, the measurement will not take place
5.2.3 Using the Hi Amp LOOP Measurement to be selected where the circuit is NOT
protected by the inclusion of an RCD
Figure 6 Hi Amp Loop – Standby screen
1. Turn the rotary switch to the LOOP / PFC position
2. Press F2 button to change from No Trip to Hi Amp
3. Connect the test leads as shown in the Figure 8
4. If voltage of the L- PE on the lower left appears,the unit is ready to TEST
5. Press the TEST button when ready
Figure 7 Hi Amp LOOP – To be used where NO RCD is present