SCHEDTXT [message text]
In the text some special symbols (tags) show the meter, timer or analog input values,
these symbols are preceded by the symbol #:
Tag
Description
#PT1 pulse meter total (not zeroable) associated with digital input 1
#T1
time meter associated to digital input 1 (display in seconds)
#T2
time meter associated to digital input 2 (display in seconds)
#T1R time meter associated to digital input 1 with autoreset after forwarding
(display in seconds)
#T2R time meter associated to digital input 2 with autoreset after forwarding
(display in seconds)
#P1
impulse meter associated to digital input 1
#P2
impulse meter associated to digital input 2
#P1R impulse meter associated to digital input 1 with autoreset after forwarding
#P2R impulse meter associated to digital input 2 with autoreset after forwarding
#D1 digital input 1 status. In the message are the words: OPEN/LO or CLOSE/HI
#D2 digital input 2 status. In the message are the words: OPEN/LO or CLOSE/HI
#O1 output 1 status. In the message are the words: ON or OFF
#O2 output 2 status. In the message are the words: ON or OFF
#AIU reading from analogue input complete with unit of measurement
#AI
reading from analogue input complete without unit of measurement
#CKS date and time of the forwarding of the last scheduled event
#CK current date and time
Timers T1 and T2 are expressed in seconds by default. The format can be changed
using the following commands.
SCHEDTXT elapsed time #T1 H  in the reply sms the time is shown in hours and
SCHEDTXT elapsed time #T1 D  in the reply sms the time is shown in days and hours
If symbols #P1 or #P2 are followed by a numeric value this is used as a multiplicative
factor for displaying the meter.
Example:
SCHEDTXT Diesel consumed today #P1 1.34 Litres
The value of the pulse meter is shown as multiplied by 1.34 and on the forwarded
message in the place of #P1 1.34 will be a number obtained by multiplying 1.34 by the
value of the pulse meter associated to digital input1.