Siemens RVL482 Instrucciones De Montaje página 34

Ocultar thumbs Ver también para RVL482:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 254
en
English
Installation and commissioning heating controller
Do not throw these instructions away but keep them with the controller!
en
Installation
Place of installation
In a dry room, e.g. the boiler room
Mounting choices:
– In a control panel (on the inner wall or on a top hat rail)
– On a panel
– In the control panel front
– In the sloping front of a control desk
Permissible ambient temperature: 0...50 °C
Electrical installation
Local regulations for electrical installations must be complied with
Only qualified staff may carry out electrical installations.
Cable strain relief must be provided
Cables from the controller to the actuator and the pump carry mains voltage
Cables to the sensors should not be run parallel to mains carrying cable (e.g. power supply
for the pump) (insulation class II to EN 60730!)
If a device is defective or damaged, immediately disconnect it from power and replace it.
Permissible cable lengths
For all sensors, thermostats and external contacts:
Copper cable 0.6 mm dia.
Copper cable 1.0 mm
Copper cable 1.5 mm
For the room units:
Copper cable 0.25 mm
Copper cable 0.5 mm
Building Technologies
max. 20 m
2
max. 80 m
2
max. 120 m
2
max. 25 m
2
max. 50 m
74 319 0619 0 a
17.04.2008
34/288

Publicidad

Tabla de contenido
loading

Tabla de contenido