Block "3-position actuator for d.h.w. / mixing circuit"
108 Actuator running
time
109 P-band of control
(Xp)
110 Integral action time
of control (Tn)
Block "Integral action time of maximum limitation of return temperature"
114 Integral action time
of maximum limita-
tion of return tem-
perature
Block "Assignment of d.h.w. heating"
121 Assignment of
d.h.w. heating
Block "Circulating pump"
122 Program for d.h.w.
circulating pump
Building Technologies
120 s
(30...873)
......................
32.0 °C
(1.0...100.0)
°C
...................
120 s
(10...873)
......................
30 min
(0...60)
min
................
0
(0...2)
.........................
2
(0...3)
.........................
74 319 0619 0 a
s
s
D.h.w. heating for
0 = own controller
1 = all controllers in the inter-
connected system that use
the same segment number
2 = all controllers in the inter-
connected system
0 = 24 h per day
1 = according to the heating
program(s), depending on
the setting made on line 121
2 = according to switching pro-
gram 2
3 = according to switching pro-
gram 3
17.04.2008
en
53/288