Maximum
continuous
input
Model
current
A
08500860
104
09501040
166
09501310
166
07600190
20
07600240
26
07600290
31
07600380
39
07600440
44
07600540
62
08600630
83
08600860
104
09601040
149
09601310
171
*
These fuses are fast acting.
**
These fuses are class gR.
***
These fuses are class HSJ.
The product is UL listed for use on a circuit up to 100 kA maximum supply symmetrical fault current,
NOTE
when protected by fuses.
IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient
NOTE
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C
(167 °F).
Table 5-1
Protective ground cable ratings
Input phase conductor size
2
≤ 10 mm
2
2
> 10 mm
and ≤ 16 mm
2
2
> 16 mm
and ≤ 35 mm
2
> 35 mm
Unidrive M200/M201/M300 Step By Step Guide
Issue Number: 2
Fuses
UL
IEC Class
Class CC,
gG or gR
*
J, or T
A
A
**
***
160
150
**
***
150
150
**
***
200
175
25
25
32
30
40
35
50
50
50
50
80
80
**
***
125
100
**
***
160
150
**
***
150
150
**
***
200
200
Minimum ground conductor size
2
Either 10 mm
or two conductors of the same cross-sectional area as the input
phase conductor
The same cross-sectional area as the input phase conductor
2
16 mm
Half of the cross-sectional area of the input phase conductor
Cables
IEC60364-5-52
2
mm
Input
Output
50
2 x 70 (B2)
2 x 35 (B2)
2 x 70 (B2)
2 x 50 (B2)
10
10
10
16
16
25
50
70
2 x 50 (B2)
2 x 35 (B2)
2 x 70 (B2)
2 x 50 (B2)
UL 508C
AWG
Input
Output
1
2 x 1
2 x 3
2 x 1
8
6
6
4
4
3
2
1/0
1/0
2 x 1
2 x 3
2 x 1/0
2 x 1
5