MAKE SURE THAT WHEN INSTALLING THE REMOTE SWITCH, THE
BATTERY IS NOT CONNECTED YET.
CAUTION
2.3
Battery requirements
For correct operation, the battery voltage should be between 0.92xVnom and 1.23xVnom
where Vnom is 12V, 24V or 48V depending on model, and must be able to supply
sufficient current to your inverter. The following table displays the recommended battery
capacity per inverter type :
Inverter type :
PS200-12
PS200-24
PS200-48
PS300-12
PS350-24
PS450-48
PS600-12
PS800-24
PS800-48
For short time inverter usage the recommended battery capacity can be halved. The inverter shuts down when the
battery voltage is below approx. 0.88xVnom or above 1.3xVnom. In a low or high battery situation the inverter is
generating one beep per second to inform you about a possible inverter shut down (except PS200-xx models). This
acoustical message will start at a battery voltage which is close to the shutdown voltage.
ALL 12V INVERTERS MUST BE CONNECTED ONLY TO A 12V BATTERY.
The inverter will not operate from a 6V battery and will be damaged
when connected to battery voltages higher than 24V.
ALL 24V INVERTERS MUST BE CONNECTED ONLY TO A 24V BATTERY.
The inverter will not operate from a 12V battery and may be damaged
when connected to battery voltages higher than 31V.
CAUTION
ALL 48V INVERTERS MUST BE CONNECTED ONLY TO A 48V BATTERY.
The inverter will not operate from a < 40V battery and may be damaged
when connected to battery voltages higher than 60V.
2.4
Connection to the battery
Unless it is absolutely necessary, TBS advises not to extend the battery wires. Extending
the battery wires may increase system losses and can cause inverter malfunctioning. If it
Iin at Pnom : Recommended battery cap. :
18 ADC
9 ADC
4 ADC
26 ADC
15 ADC
7 ADC
47 ADC
29 ADC
14 ADC
8
50 Ah
30 Ah
20 Ah
100 Ah
60 Ah
30 Ah
200Ah
120Ah
60Ah