Ingersoll Rand QC100 Manual Del Usuario página 6

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11
EN
Operation Flowchart Admin Setup for QC100 (Cont'd)
...ADMIN MENU...
PRESSURE ALARM
...ADMIN MENU...
ALARM TRIP #
...ADMIN MENU...
FLOW HI LIMIT
...ADMIN MENU...
FLOW LOW LIMIT
...ADMIN MENU...
FLOW FAULT LIMIT
EN-5
PRESSURE: 0
FLOW: 2791 READY
ALARM TRIP #
#: 1
HI LIMIT: 4305
FLOW: 49396 READY
LOW LIMIT: 4095
FLOW: 49396 READY
FLOW FAULT LIMIT
LIMIT: 10
END
Use UP/DWN arrow to adjust the flow reading at which the low
pressure alarm will sound. It is recommended that you run
down fasteners below your operating pressure, and adjust the
alarm setting to the average flow reading at the low pressure
condition.
Use UP/DOWN arrows to select Alarm # 1-10.
Goes from 0 to 5000 (not CFM, just scale). Required when there
is a need to detect air leakage in vent.
Goes from 0 to 5000 (not CFM, just scale). Required when there
is a need to detect air leakage in vent.
Goes from 1 to 10 count.
45498318_ed1