Modbus Communication Leds - Fronius Smart Meter 240V-3 UL Manual De Instrucciones

Monitorización de instalaciones
Ocultar thumbs Ver también para Smart Meter 240V-3 UL:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Meter Not Operating
If none of the LEDs are illuminated, check that the correct line voltages are applied to the
meter. If the voltages are correct, call customer service for assistance.
Error
If the meter experiences an internal error, all LEDs will light up red for 3 or more
seconds. If you see this happen repeatedly, call customer service for assistance.
Modbus Commu-
Near the upper left corner, there is a diagnostic Com (communication) LED that can
nication LEDs
indicate the following:
18
A short green flash indicates a valid packet addressed to this
device.
Short yellow flashes or rapid flashing indicate valid packets
addressed to different devices.
A one-second red flash indicates an invalid packet: bad baud
rate, bad CRC, noise, bad parity, etc.
Rapid red/yellow flashing indicates a possible address con-
flict (two devices with the same DIP switch address).
Solid red indicates the address is set to zero: an invalid
choice.

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smart meter 480v-3 ulSmart meter 600v-3 ul

Tabla de contenido