Efficiency And Power Limitation - Aros SIRIO EVO Manual De Instalacion Y Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

LCD message
'L01 Data bus KO'
'L02 Memory fault'
'L03 Wrong nation'
'L04 CPU fault'
'L05 Wrong size'
'L06 FW mismatch'
'L07 Supply fault'
'L10 GFCI fault'
'L11 CONT_INV KO'
'L12 CONT_GRD KO'
'L09 GFCI leakage'
'L15 FW error'
'L16 OFF command'
'L17 ADC fault'
'L18 Vac mismatch'
'L19 Fac mismatch'
'L20 Igf mismatch'
'L21 Autotest KO'
'L22 Reverse grid'
'L28 Iac sens. KO'
E
FFICIENCY AND POWER LIMITATION
The inverter limits its output power in the following situations:
PV generator power exceeds maximum inverter power
MPP current on the PV generator is higher than the "Max. input current". See "Figure 1" in the Appendix.
The gird voltage is less than the "Minimum voltage at rated power". In this case, the inverter limits output current to
"Max. output current".
Inverter temperature exceeds the "Rated power temperature range": in this case, the inverter reduces the output power.
In the cases provided for by local regulations: see the „INFORMATION‟ menu paragraph.
In all the aforementioned cases, the yellow LED lights up on the inverter.
Description
Communication problems with memory and internal
clock.
Problem with internal memory containing inverter
settings
Problem with internal memory containing inverter
settings
Communication
problem
microprocessors
Problem with internal memory containing inverter
settings
Incompatible firmware loaded on microprocessors
The inverter auxiliary power not working properly
Inverter differential sensor fault
Relay fault
Attempts to reconnect run out because of a ground
leakage.
The DSP have performed an operating error.
The inverter has received a remote shutdown
command. It remains in this state until receiving an
unlock command (remote or manual)
Analogue readings reference fault
Grid voltage reading does not match between the
two microprocessors
Grid frequency reading does not match between the
two microprocessors
Leakage current reading does not match between
the two microprocessors
The autotest procedure was not successful: one or
more thresholds or response times were incorrect.
Phase and neutral reversed on the AC connector in
the single phase inverters
Output current sensor fault
Inverter faults
Contact technical assistance
Reset the nation using the specific menu.
Switch the inverter off and back on again.
between
the
two
Contact technical assistance
Check the system
Manually
'COMMANDS' Menu paragraph). If this
does not work, contact technical assistance
Manually
'COMMANDS' Menu paragraph).
Contact technical assistance
Manually
'COMMANDS' Menu paragraph). If this
does not work, contact technical assistance
Repeat autotest
Correct wiring
Contact technical assistance
- 61 -
Proposed action
start
the
inverter
start
the
inverter
start
the
inverter
(see
(see
(see