Relays, contactors, solenoids or coils of electromechanical brakes installed close to the output
inverters may occasionally generate interferences in the control circuitry. To eliminate this
effect, RC suppressors (with AC power supply) or freewheel diodes (with DC power supply)
must be connected in parallel to the coils of these devices.
The rated operating voltage of the DBW04 is configured by means of the DIP switch S1,
located on the CDB1 board. A model of line 600 V (DBW040250D5069SZ) can be adjusted
for three different voltage ranges: 500 - 525 V, 550 - 575 V, 600 V or 660 - 690 V, see
3.3 on page
21.
Position S1
ON
0
1 2
ON
1
1 2
ON
2
1 2
ON
3
1 2
(*) Factory setting.
The setting of the braking actuation voltage is also performed on the CDB1 board; however,
by means of the DIP switch S2. The values of voltage levels are presented in
22. As factory setting, the braking actuation voltage is 20 % above the link rated voltage.
Figure 3.9: Shield connection
Table 3.3: Setting of S1 (setting of the rated voltage)
S1:1
S1:2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
(*)
Installation and Connection
Insulate with tape
Side of the
braking module
Do not ground
380 - 480 V
380 V
400 - 415 V
440 - 480 V
(*)
(*)
Table
500 - 690 V
500 - 525 V
550 - 575 V
600 V
660 - 690 V
(*)
Table 3.4 on page
DBW04 | 21