Technical Specifications

7 TECHNICAL SPECIFICATIONS
This chapter describes the technical specifications (electric and mechanical) of the DBW04.

7.1 POWER DATA

Table 7.1: Technical specifications for the DBW04 braking module
Line
Model
(Vac)
DBW040380D3848 380-480
DBW040250D5069 500-690
(1) Disregarding the power dissipated on the braking resistor.
Note:
(1) Steady state rated current in the following conditions:
- Temperature around the braking module: -10 °C (14 °F) to 45 °C (113 °F). The braking
module can operate at ambient temperatures up to 55 °C (131 °F) if the output current is
derated by 2 % for each degree Celsius above 45 ºC (113 °F).
- Relative air humidity: 5 % to 95 % non-condensing.
- Altitude: 1000 m (3.300 ft). Above 1000 m (3.300 ft) up to 4000 m (13.200 ft) the output
current must be derated by 1 % for each 100 m (330 ft) above 1000 m (3.300 ft).
From 2000 m to 4000 m (6.600 ft to 13.200 ft) above sea level - maximum voltage reduction
(690 V for 500...690 V models) of 1.1 % for each 100 m (330 ft) above 2000 m (6.600 ft).
- Ambient with pollution degree 2 (according to EN50178 and UL508C).
(2) The specified losses are valid for rated operating conditions, that is, for rated output current.

7.2 ELECTRONICS / GENERAL DATA

Inputs (CDB)
Digital
Outputs (CDB1 Board)
Relay
Safety
Protection
Enclosure
IP00

7.2.1 Codes and Standards

Safety standards
Mechanical standards
30 | DBW04
Braking
Overvoltage
Actuation
Fault (Vdc)
Level (Vdc)
588-792
800
816-1188
1200
1 insulated input and 1 thermostat input
2 relay outputs with NO/NC contacts, 240 Vac, 1 A
Under/Overvoltage
Overtemperature on the heatsink and braking resistor
Overcurrent
Ground fault
UL 840 - Insulation coordination including clearances and creepage distances for electrical
equipment.
EN61800-5-1 - Safety requirements electrical, thermal and energy.
EN 50178 - Electronic equipment for use in power installations.
EN 60146 (IEC 146) - Semiconductor converters.
EN 60529 - Degrees of protection provided by enclosures (IP code).
UL 50 - Enclosures for electrical equipment.
Rated
Braking
Minimum
Effective
Power
Resistance
Current on
(kW)
(Ω)
the Module
(A)
301
1.8
380
297
2.6
250
Peak
Dissipated
Current
Power
(A)
(kW)
(1)
440
1.00
457
1.00