Safety Manual
14 Safe parameterisation - user responsibility
14.1 Safety-related configuration parameters
Parameters
CH1.FUN
CH2.FUN.
PASSW
The above safety-related configuration parameters are marked in red
text in the routing diagrams and must be verified by the user in a SIL-
configuration.
14.2 Verification procedure
The verification is done using the display / programming front PR 4501
by following the procedure described below.
14.2.1 If no password is set
1
2
3
4
5
6
7
8
9
10
* Open is shown briefly in the display.
8
9203 Solenoid / Alarm Driver
Value
DIR / INV
DIR / INV
0 - 9999
Action
Press OK
Set (ADV.SET) to Yes and press OK
Step down to (SIL SETUP) and press OK
Set (EN SIL) to YES and press OK
Set password to a number between 0 and
9999 and press OK
(At this time the device starts operating in
SIL mode with the entered configuration
parameters!)
Press OK to confirme verification of the
OPEN-LOCK in the display
Verify Channel 1 function and press OK
Verify Channel 2 function and press OK
Verify password and press OK
Verify SIL and press OK
Version No. V5R0
Description
Direct / inverted channel function
Direct / inverted channel function
New password
Display shows
ADV.SET
DISP SETUP
EN.SIL
NEW.PASS
Verify OPEN
"briefly"
LOCK*
CH1.FUN
CH2:FUN
PASSW
SIL.OK