Balluff BAE PS-XA-1S-24-200-104 Manual De Instrucciones página 15

Ocultar thumbs Ver también para BAE PS-XA-1S-24-200-104:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Switching mode power supplies IO-Link ready
BAE PS-XA-1S-24-200-104
IO-Link Interface (only together with Clip-On BAE SC-AE-I01)
General device information
Baud rate
Process data length input
Minimum cycle time
IO-Link version
SIO mode
IO-Link mode (communication mode)
If the Clip-On BAE SC-AE-I01 is installed IO-Link
communication is possible via its Pin 2.
Process data
The process data is 32 bits in length. Included in the
process data are the switching states of the 4 switching
outputs (BDC1...BDC4), one bit for the On/Off state of the
PSU, as well as the current readings for voltage and
current.
31...20 Bits
19...8
7 6...4
Error codes
Error code
0x8011
0x8012
0x8023
0x8030
Parameter Value out of Range
0x8033
Paremeter length overrun
0x8034
Parameter length underrun
0x8035
www.balluff.com
COM 2 (38.4 kBaud)
4 bytes
20 ms
V1.1
no
3
2
1
0
Description
Index not available
Subindex not available
Access Denied
Function not available
Event codes
Definition
Event
codes
IO-Link
IO-Link
1.1
No malfunction 0x0000
0x0000
General
0x1000
0x1000
malfunction.
Unknown error
Process
0x8C10
0x8C10
variable range
over-run.
Process Data
uncertain
Process
0x8C30
0x8C30
variable range
under-run.
Process Data
uncertain
PSU
0xB000
0x1800
disconnected
from Clip
Bad
0xB001
0x1801
connection
between PSU
and Clip
PSU changed
0xB004
0x1804
High stress
0xB005
0x1805
level
Fast aging
0xB006
0x1806
Over
0xB007
0x1807
Temperature
Overload
0xB008
0x1808
Overvoltage
0xB009
0x1809
Output drop
0xB00A
0x180A
Event
Device
Type
codes
status
1.0
0
Notifi-
cation
4
Error
2
Warning
2
Warning
4
Error
4
Error
2
Error
1
Warning
1
Warning
2
Warning
2
Warning
2
Warning
2
Warning
english
5

Publicidad

Tabla de contenido
loading

Tabla de contenido