Minimum distance to reflective surfaces
WARNING
Failure to maintain minimum distances
to reflective surfaces may result in serious injury!
 Determine the minimum distance (see figure
 Make certain that all reflective surfaces are the necessary minimum distance
away from the protective field according to prEN IEC 61496-2 (see figure
).
3
 Check that reflective surfaces do not impair the detection capability of the
safety sensor before start-up and at appropriate intervals.
2
a Required minimum distance to reflective surfaces [mm]
b Protective field width [m]
c Reflective surface
3
a Required minimum distance to reflective surfaces [mm]
b Protective field width [m]
Assembly
 Mount the IP protective tube on the end caps.
To do this, use the mounting brackets included in the scope of delivery.
Tightening torque of the mounting screws: 3 Nm
 Mount the transmitter or the receiver with the IP protective tube to the system
using the mounting brackets.
 Electrically connect the transmitter or the receiver via the connection cable of the
IP protective tube.
 Align the transmitter and receiver with one another – see chapter
ing
original operating instructions
in the
10
).
2
for the MLC.
Commission
-