Fitting Instructions - NORMA CONNECT FGR GRIP Instrucciones De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 6
FGR GRIP / GRIP E / GRIP E-FP

Fitting Instructions

Sealing axial tensile pipe coupling for metal pipes with Ø 26.9 - 711 mm.
1.
EPDM
-30 °C...+125 °C
T °C
Ø 26.9-168.3 mm
-20 °C...+80 °C
Ø 180-711.2 mm
2.
EPDM
20
Ø 26.9-711.2 mm
15
25
10
30
The max. permissible pressure levels for shipbuilding and industrial applications are stated on the pipe coupling's label.
5
35
bar
For sprinkler and water-based extinguisher systems „VdS": Ø
0
40
33.7-88.9 mm 16 bar,
Ø 114.3 mm 12.5 bar, Ø 139.7 mm 10 bar
3.
EPDM
For water, air and solids.
4.
If there is a risk of corrosion, use
bolts and bars made from stainless
steel (CrNi). To protect couplings in
the long-term, use shrink sleeves or
protection tapes.
5.
DISTANCE BETWEEN PIPE ENDS
Ø 26.9 – 33.7 mm
Ø 35.0 – 48.3 mm
Ø 54.0 – 60.3 mm
Ø 76.1 – 114.3 mm
C
max
Ø 133.7 – 711 mm
6.
AXIAL MISALIGNMENT
max
≤ 1 % OD, but max. 3 mm
(Rectify greater misalignment by means of angular deflection.)
7.
ANGULAR DEFLECTION α
C
max
2° for all Ø in all directions.
α
(Distance between pipe ends C
max
8.
PIPE OVALITY
≤ 2 % OD, but max. 5 mm
(Applies to two pipes of similar ovality only.)
max
9.
OUTER DIAMETER DIFFERENCES
≤ 2 % OD, but max. 5 mm
min
max
10.
The specified tolerances must not be exceeded or combined. They refer to static loads and radially rigid pipes.
A safety factor has to be included for dynamic loads such as pressure surges, external forces, etc.
(Contact manufacturer for further information.)
11.
THE FOLLOWING INFORMATION (11-15) MUST BE OBSERVED! 
Remove burrs and clean pipe ends. Damage such as scratches, cracks, etc., or coatings such as paint, rust, etc., must be
removed from the sealing lip area.
2
NBR
-20 °C...+80 °C
Ø 26.9-711.2 mm
NBR
Ø 26.9-711.2 mm
NBR
For gases, oils and fuels.
Note: When used in sprinkler and
water-based extinguisher systems, special flame protection
is needed. In such cases, the coupling is marked as „VdS".
C
max
C
max
C
max
C
max
C
max
must be observed.)
max
www.normagroup.com
= 3 mm
= 8 mm
= 17 mm
= 25 mm
= 35 mm

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Connect grip eConnect grip e-fp