4. Commissioning
4.1 Supply pressure
4.2 Jet pressure
7313157-02 02.14
Supply Pressure
The supply pressure must lie between the following values:
for natural gas:
- min. 18,0 mbar
- max. 25.0 mbar
For LPG:
- min. 42,5 mbar
- max. 57,5 mbar
The supply pressure is measured as pressure in the gas flow at the measuring nozzle
of the gas valve.
The boiler must not be started up when the supply pressures are outside the said
range. The gas supply company should be informed.
Guide values for injector pressure (full load)
Model
Nominal heat load
Nominal heat output
Injector diameter for
Natural Gas LL (G25)
Natural gas E (G20)
LPG (propane)
Gas type
- G25 (12,4)*
- G20 (15,0)*
- Propane
- Butane
CO
-Content
2
* values in brackets: Wobbe index WO
** at pressure at end of boiler 0 mbar, 1013 hPa, 15 °C
1)
with burner pipe Stainless Steel
2)
with mesh burner Furinit
Gas valve CG 15 R03 VW5 WZ
SGB 90 C
Heating
kW
25,0 - 90,0
80/60°C
kW
24,2 - 86,7
50/30°C
kW
26,4 - 92,3
mm
mm
mm
Guide values for injector pressure **
mbar
9,0 - 12,0
mbar
6,0 - 8,0
mbar
8,5 - 10,5
mbar
Natural
%
8,0 - 8,5
gas
LPG
%
9,5 - 10,0
3
in kWh/m
N
Commissioning
1)
2)
SGB 90 C
/D
22,5 - 90,0
21,8 - 86,7
23,8 - 92,3
8,50
9,00
7,80
8,00
6,20
6,20
(full load)
10,9 - 12,2
11,0 - 12,4
12,7 - 14,0
9,7 - 10,7
8,7 - 9,3
10,5 - 11,0
25