Connection example
Limit value contact LV 1
switches mains voltage
n
3
4
5
e.g.
solenoid
valve
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Maintenan
18
19
16

Connecting the plant components

 Connect the plant components to the output terminals of relays 1
to 19 (e.g. valves).
 If the plant components require mains voltage, connect the
switched mains voltage (l) to the common contact
l
PE
respective relay (see the connection example for 230 VAC on the
left).
 Connect the neutral conductor of the plant component to one of the
terminals (n).
 For components with a protective earth conductor connection,
connect it to the PE connection.
 Ensure that the leads are held securely in the terminals.
Type Function
Terminal
Flush
OUT External flush valve
Limit value output 1 – N/C
Limit value output 1 – N/O
LV1
OUT
Limit value output 1 - Common
Limit value output 2 – N/C
Limit value output 2 – N/O
LV2
OUT
Limit value output 2 - Common
Measuring point 1 – N/C
M. point.
Measuring point 2 – N/O
OUT
1/2
M. point switch-over - Common
AUX
OUT Universal output
Fault message output – N/C
Fault message output – N/O
Alarm
OUT
Fault message output - Common
Maintenance message – N/C
Maintenance message – N/O
OUT
ce
Maintenance message - Common
Installation
of the
Comment
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max,
max. 240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A
Isolated relay output, max.
240 VAC, 4 A