Quick Start Process; Installation Following A Period Of Storage - SODECA VSD1/A-RFM-0.5 Manual De Instalación Y Operación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1.2. Quick Start Process

Step
1
Identify the Enclosure Type, Model Type and ratings
of your drive from the model code on the label. In
particular
-
Check the voltage rating suits the incoming
supply
-
Check the output current capacity meets or
exceeds the full load current for the intended
motor
2
Unpack and check the drive. Notify the supplier and
shipper immediately of any damage.
3
Ensure correct ambient and environmental
conditions for the drive are met by the proposed
mounting location.
4
Install the drive in a suitable cabinet (IP20 Units),
ensuring suitable cooling air is available. Mount the
drive to the wall or machine (IP66).
5
Select the correct power and motor cables according
to local wiring regulations or code, noting the
maximum permissible sizes
6
If the supply type is IT or corner grounded,
disconnect the EMC filter before connecting the
supply.
7
Check the supply cable and motor cable for faults or
short circuits.
8
Route the cables
9
Check that the intended motor is suitable for use,
noting any precautions recommended by the
supplier or manufacturer.
10
Check the motor terminal box for correct Star or
Delta configuration where applicable
11
Ensure suitable wiring protection is providing, but
installing a suitable circuit breaker or fuses in the
incoming supply line
12
Connect the power cables, especially ensuring the
protective earth connection is made
13
Connect the control cables as required for the
application
14
Thoroughly check the installation and wiring
15
Commission the drive parameters

1.3. Installation Following a Period of Storage

If the drive has not been powered, either unused or in storage, the DC Link Capacitors require reforming before power may be connected to the
drive. Refer to your local sales partner for information regarding the correct procedure.
Action
See Section
2.1
Identifying the Drive by Model Number
9.1
Environmental
3.1
General
3.3
Mechanical Dimensions and Mounting – IP20 Open Units
3.4
Guidelines for Enclosure Mounting – IP20 Units
0.5
Mechanical Dimensions – IP66 (Nema4X) Enclosed Units
3.6
Guidelines for Mounting (IP66 Units)
9.2
Rating Tables
9.5
EMC Filter Disconnect
4.6
Motor Terminals Box Connections
9.2
Rating Tables
4.1
Grounding the Drive
4.3
Wiring Precautions
4.4
Incoming Power Connection
4.8
Control Terminal Wiring
4.9
Connection Diagram
7
Analog and Digital Input Macro Configurations
5.1
Managing the Keypad
6
Parameters
4
Page
6
28
7
7
8
9
9
27
28
13
28
11
12
12
14
15
22
16
17

Hide quick links: