Connection method of the connecting cable (Example)

1. Make a hole appropriate for the passage of connection cable through on cap by tool.
2. After knocking out the holes, we recommend you paint the edges and areas around the edges using
the repair paint to prevent rusting
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with the cord clamp providing on the unit not to have strain at the terminal.
6. Finally, Fix the cap to the conduit panel.
Model name
ARUN076DT2 ARUN096DT2 ARUN115DT2 ARUN134DT2 ARUN154DT2
AWG
14
Conduit (inch)
1/2
Knockout Diameter (inch)
7/8
Model name
ARUN173DT2 ARUN192DT2 ARUN211DT2 ARUN230DT2 ARUN250DT2 ARUN270DT2
AWG
12
Conduit (inch)
1/2
Knockout Diameter (inch)
7/8
Model name
ARUN076BT2 ARUN096BT2 ARUN115BT2 ARUN154BT2 ARUN173BT2 ARUN192BT2
AWG
10
Conduit (inch)
1/2
Knockout Diameter (inch)
7/8
WARNING
• Loose wiring may cause the terminal to overheat or result in unit malfunction.
• A fire hazard may also exist.
• Therefore, be sure all wiring is tightly connected.
14
14
12
1/2
1/2
1/2
7/8
7/8
7/8
12
12
10
1/2
1/2
1/2
7/8
7/8
7/8
10
8
6
1/2
1
1
7/8
1-23/64
1-23/64
Electrical Wiring
12
1/2
7/8
ARUN290DT2 ARUN310DT2
8
8
6
1
1
1
1-23/64
1-23/64
1-23/64
ARUN211BT2 ARUN230BT2
6
4
4
1
1-1/4
1-1/4
1-23/64
1-23/32
1-23/32
Installation Manual 57
6
1
1-23/64
4
1-1/4
1-23/32