Contact Input Switch Wiring
This section describes the wiring for dry contact closure
devices. There are two switch input wiring terminals on the
left side of the ControlKeeper 2 to allow for wiring of the
dry contact closure devices.
1.
Use 18 AWG twisted, unshielded wire for all low
voltage dry contact closure device wiring.
2.
Maximum length for dry contact closure device wiring
is 1000 feet.
3.
Please see wiring detail below for details on
connections of different devices to the ControlKeeper 2
system.
Low Voltage
Switch Inputs
Momentary Switch
(3 Wire)
Toggle Switch
(2 Wire Momentary)
ControlKeeper 2 Low Voltage Switch Wiring
Contact Input Photosensor and Greengate Sensor
Notes
It is possible to use a contact input photosensor and
Greengate Motion Sensors in conjunction with the lighting
control system. The ControlKeeper 2 is capable of powering
a number of these devices. Please refer to the chart below
for details on how many devices the transformer can
support.
Greengate
Greengate
PIR Sensor
Dual-Technology
Sensor
40
16
Please contact technical support if it is necessary to power
additional sensors beyond the numbers listed above. These
figures do not account for additional devices such as digital
switches being used. If using a combination of devices,
please contact technical support for exact details on how
many devices the logic panel can power.
ControlKeeper® 2
Additional Switch Types
ON
Maintained Switch
+24
CH1
OFF
(2 Wire)
ON
+24
CH2
OFF
Greengate
PPS-4
Ultrasonic
Indoor
Sensor
Photosensor
20
20
Low Voltage
Switch Inputs
PPS4
Photosensor
Black
Black
Typical Greengate
Motion Sensor Wiring
REM PWR DC GND
(Black Wire)
ON
+24
CH1
Digital Switch Wiring
OFF
Each ControlKeeper 2 panel is capable of supporting up to
CH2
7 digital switch device stations and 1 GDS-I gateway device
(the number the controller is able to support is dependent
on the number of other low voltage devices wired that
require power from our logic board. Please contact technical
support for exact details of how many devices your logic
board can power.)
Digital switch cable type should be Cooper Lighting
Solutions LC Cable, Belden 1502R (non-plenum), or Belden
1502P (plenum).
For best network performance, one of the suggested
cables should be used. If the specified cable is not used
and communications problems occur that require
troubleshooting assistance, additional charges for support
may be assessed.
Digital switches do not wire directly to the ControlKeeper 2
panel, but are wired to a CAN Bus network that connects to
PPS-5
the ControlKeeper 2 through a GDS-I device. Digital switch
Outdoor
devices should be networked together in a daisy-chain
Photosensor
configuration. No T-Taps/Stars should be used. The GDS-I
4
device should reside somewhere within the daisy-chain
switch network. Total daisy-chain network length should not
exceed 1000 feet.
The following instructions describe the GDS-I device
connection to the ControlKeeper 2. Please refer to the GDS
installation instructions for information on wiring the digital
switch network to the Digital Switch Gateway.
1.
Mount the GDS-I next to the ControlKeeper 2 panel.
A six foot phone style cable has been provided for
connection to the ControlKeeper 2 panel.
General Information
ON (Blue Wire)
ON
ON
+24
CH1
+24
+24 VDC (Red Wire)
OFF
OFF
ON
ON
+24
+24
CH2
OFF
OFF
GND
GND
Photosensor and Motion Sensor Wiring
PPS5
Photosensor
ON (White Wire)
Black
+24 VDC (Red Wire)
REM PWR DC GND
(Black Wire)
3