Network
Network
Network
Network Addressing
Assign each panel a network address. A network address is
required for the ControlKeeper 2 to communicate over a
network and for programming with the Lighting Control
Software. A selector switch is provided on the panel to
assign the panel ID number.
Switch positions are labeled 1 through 8 and valued at 1
through 128. The ID # is calculated by adding the values of
each position that is ON. Addresses 1 through 254 are valid
addresses. Zero is not a valid address. In addition, address
255 is reserved for system use and should not be used as a
panel address.
N
ote:
Each ControlKeeper 2 must have a unique address.
If networked with other ControlKeeper panels, each
panel must have a different address.
2
3
1
Switch
Position
Value
1
2
4
To initialize the ID# within the ControlKeeper 2, it is
necessary to do a reset. Press the panel-reset button
located on the lower left side of the panel after setting the
panel address.
ControlKeeper® 2
Network Terminator
in Place
End Panel Network
Wiring Detail
Network Terminator
Removed
Middle Panel Network
Wiring Detail
Network Terminator
in Place
End Panel Network
Wiring Detail
4
5
7
8
6
8
16
32
128
64

Applying Power:

1.
Once the wiring is complete, make certain that the
enclosure is clean of any wire clippings and that no
fragments are lodged in the relay circuit boards.
2.
Ensure that there are no loose wires or exposed wires
that could short to other wires or components.
3.
Power up the unit from the circuit breaker.
4.
Once power is applied to the unit, lighting loads may be
operated via the ALL ON / AUTO / ALL OFF switch as
necessary.
Manually Controlling Relays
The relays in the enclosure may be controlled before the
logic board is programmed by using the on-board, ALL OFF ,
AUTO, ALL ON switches. In the ALL ON position, the relay
coils will be energized. In the ALL OFF position, the relay
coils will be de-energized. The middle, AUTO, position allows
the relays to be controlled by the individual relay switches or
from the logic controller.
System Reset and Clear Commands
Under certain circumstances, you may want to reset the
ControlKeeper 2. There are two different types of reset
commands available in the ControlKeeper 2 system: a Soft
Reset Command and a clear reset command.
Soft Reset Command:
The Soft Reset Command reboots the microprocessor. It
will not cause loss of panel programming. To perform a Soft
Reset Command, press and release the reset button.
Clear Settings Command:
A Clear Settings Command is used to remove all
programming from a ControlKeeper 2 unit. It should be
done before programming the unit for the first time or
when asked to by a technical support representative. Please
use caution with this command! When performing a Clear
command, all relay loads will turn OFF . Use the ALL ON
override switch to keep lighting ON if necessary.
To perform a Clear Command:
Press and hold the reset button for at least 20 seconds. The
status LED will start flickering. Release the reset button. The
unit is now cleared to factory default programming.
LED Operation
The ControlKeeper 2 has LEDs mounted on the left side of
the panel. Refer to the diagram at the beginning of these
instructions for the location of these LEDs.