Lighted Switch Notes
1.
You must use lighted switches that have been approved
for use with the ControlKeeper T system.
2.
The panel's onboard power supply can support up to
75 LED lighted switches in a CKT16 enclosure, 45 LED
lighted switches in a CKT32 enclosure and 30 LED
lighted switches in a CKT48 enclosure. Please contact
technical support if it is necessary to power additional
switches beyond the numbers listed above. No more
than 6 LEDs may be run per input channel.
3.
The panel's onboard power supply can support up to 38
incandescent lighted switches in a CKT16 enclosure,
23 incandescent lighted switches in a CKT32 enclosure
and 15 incandescent lighted switches in a CKT48
enclosure. Please contact technical support if it is
necessary to power additional switches beyond the
numbers listed above. No more than 3 incandescent
bulbs may be run per input channel.
4.
Please note that these figures may decrease if motion
sensors, photocells or digital switches are being used
with the controller. In addition, if switch types are
mixed (incandescent and LED being used on the same
controller), these figures will change. Please contact
technical support with the numbers and types of inputs
you are using to determine if the controller will be able
to support them without overloading the power supply.
Lighted Switch Wiring Detail
Contact Input Photosensor and Greengate
Sensor Notes
It is possible to use a contact input photosensor and
Greengate motion sensors in conjunction with the lighting
control system. The ControlKeeper T enclosures are capable
of powering a number of these devices. Please refer
to the chart below for details on how many devices the
transformer can support.
Enclosure
Greengate
Greengate
Size
PIR Sensor
Dual-Technology
Sensor
CKT 16
150
CKT 32
90
CKT 48
90
ControlKeeper® TouchScreen Logic Board
Greengate
PPS-4
Ultrasonic
Indoor
Sensor
Photosensor
60
75
75
36
45
45
24
30
30
Please contact technical support if it is necessary to power
additional sensors beyond the numbers listed above.
These figures do not account for additional devices such as
lighted switches or digital switches being used. If using a
combination of devices, please contact technical support for
precise limits on the number of devices the logic panel can
power.
Digital Switch Wiring
ControlKeeper T panels are capable of supporting a number
of digital switch device stations and 1 GDS-I gateway device
(the number the controller is able to support is dependent
on the number of other low voltage devices wired that
require power from our logic board. Please contact technical
support for exact details of how many devices your logic
board can power.) Refer to the chart below for the number
of digital switch device stations based on panel size. Digital
switch cable type should be Cooper Lighting Solutions'
Cable, Belden 1502R (non-plenum), or Belden 1502P
(plenum).
CKT16
CKT32
CKT48
PPS-5
Outdoor
For best network performance, one of the suggested
Photosensor
cables should be used. If the specified cable is not
15
used and communications problems occur that require
9
troubleshooting assistance, additional charges for support
may be assessed.
6
Lighted Switch Notes
Photocell and Motion Sensor Wiring
32 Devices
Including a GDS-I
18 Devices
Including a GDS-I
12 Devices
Including a GDS-I
3