System Reset and Clear Commands
System Reset and Clear Commands
Under certain circumstances, you may want to reset the
ControlKeeper T. There are two different types of reset
commands available in the ControlKeeper T system: a Soft
Reset Command and a Clear Reset Command.
Soft Reset Command:
A Soft Reset Command is used to
initialize a new panel address with the panel. It can also
be used as a troubleshooting technique if the panel is not
responding or to free up the microprocessor if the unit's
Status LED is not flashing. The Soft Reset Command will
not cause loss of panel programming. To perform a Soft
Reset Command, press in and then immediately release
the reset button in the upper left corner of the logic panel.
(Refer to Figure 16 item reference for location of the reset
switch.) When the reset button is pressed and released,
the status LED may hesitate briefly then resume normal
operation. In addition, the display may go blank then
re-initialize. The ControlKeeper T will issue the last known
command to the relays upon each reset.
Clear Settings Command:
to remove all programming from a ControlKeeper T
unit. It should be done before programming the unit for
the first time or when asked to by a technical support
representative. Please use caution with this command!
When performing a Clear command, all relay loads will turn
OFF . Use the RSC Override Switch to keep lighting ON if
necessary.
To perform a Clear Command: reset the panel, using the
reset button. Refer to the item reference diagram Figure
16 for the location of the reset button. Wait for the Status
LED to start flashing again. Within one minute, touch all 4
corners of the display screen, one corner after the other,
going clockwise, being sure not to touch anywhere else on
the screen. If more than a minute goes by without all four
corners being touched, or if you touch anything other than
the four corners, you will leave the memory clear function.
After you have touched the four corners within the one
minute time period, a warning message asking if you really
want to clear the panel will appear. Press YES if you want
to clear the panel memory; press NO if you do not want to
clear the memory.
Programming the ControlKeeper T
The ControlKeeper T is programmed either through the
TouchScreen onboard interface or through the optional
Keeper Enterprise Software. Please refer to Programming
Guide that came with the unit to program via the
touchscreen or to your Keeper Enterprise Manual for
programming details. It is recommended that a Clear
Command be performed on the controller before the first
programming is done to clear any test data that may be left
in the controller from factory testing.
10
ControlKeeper® TouchScreen Logic Board
A clear settings command is used
Repair Information
If a repair becomes necessary on your ControlKeeper T unit,
please refer all service to Greengate technical support line
at 1-800-553-3879. Should you be directed to return your
logic board to the factory for service please follow the steps
below.
1.
Label all wiring.
2.
Put the relay override switch on the RSC to the ALL ON
position.
3.
Unplug the logic board communications cable (red
CAT5 cable) from the RSC.
4.
Unplug the logic board power wiring (white connector)
from the RSC.
5.
Remove input terminal blocks, Digita
connections, Network wiring and TB2 power terminal
block, if used.
6.
Unlatch upper spring hinge to swivel logic board down.
7 .
Release both spring hinges at sides of logic board and
remove board.
8.
Package the logic board carefully for shipment to
factory.
W
ARNING:
Damage Caused by improper packaging will
not be covered by warranty.
Operation Notes
The ControlKeeper T consists of a logic board and an
enclosure. There are several features of note as pointed out
in the following item reference diagrams.
Switch
®