4.
Plug the communications cable (red CAT5 Cable
provided) into the Relay Stack Controller Card (RSC)
located at the bottom of the enclosure. This cable can
be plugged into either of the two RJ45 jacks located on
this board. See Figure 8 below.
Figure 8. RSC Communications Cable Connection
5.
If lighting needs to be ON during the next steps, make
certain that the RSC override switch has been used to
override the lighting ALL ON. Press the Reset button
located in the upper left corner of the logic panel.
This will initialize a system reset, causing the relays to
assume to panel's state. (If unit is being powered for
the first time without being programmed, the relays
will turn OFF unless the RSC override switch is used to
override lighting ALL ON prior to the reset being hit.)
Figure 9. CKT Reset Button
ControlKeeper® TouchScreen Logic Board
Relay Override Operation
The ControlKeeper T has two means of overriding relays
ON or OFF without the need of the logic board in place.
First, there are individual relay override buttons for each
relay located on the relay hardware. Second, there is an
all enclosure override switch located at the bottom of
the enclosure. It is possible to control lighting loads and
override programming using these override mechanisms
without the logic board being in place.
Individual Relay Override Notes
The individual relay overrides are located in the high voltage
section of the controller. If you are not an electrician, or
rated for work in a high voltage environment, it is not
recommended that you access these switches from a
safety concern.
Each relay on the ControlKeeper T may be overridden using
the individual relay override switches located at the top
left of the low voltage section. See Figure 10 for location
of these switches. These override switches will toggle the
associated relay's state with each push of the button. This
type of override is temporary in that the override will last
until the next command that the relay is given.
Figure 10. Relay Override Switches
Relay Override Operation