C) Ct Position Checking - Alpes Technologies ALPIMATIC Manual De Instalación

Baterías de condensadores equipadas con regulador alptec 8
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

C – CT POSITION CHECKING
In case of wrong cos phi reading by the controller, it is necessary to check its position to make sure it is
properply located on phase L1 and upstream all the loads to be compensated.
To do :
By means of a voltmeter check there is zero voltage between phase L1 of the network where CT
is fitted and phase L1 of capacitor bank
P1
L1
C.T
L2
L3
network
________________________________________________________________________________
.
P2
V
U = 0 V
Page 29
_
Capacitor bank busbar
L1
L2
L3

Publicidad