Functionning In Manual Mode - Alpes Technologies ALPIMATIC Manual De Instalación

Baterías de condensadores equipadas con regulador alptec 8
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

You can, if you wish, make the capacitor bank work in manual or « forced » mode.
Please process accordingly :
If you are on the main page press
Switch to manual mode by selecting
All steps under voltage are disconnected
You're back to the main page
Press
or
key as many times as neccessary to select the step you want to connect or
disconnect : the selection is done when a rectangle appears below the step number
Press
key to connect the step
Press
to disconnect thte step
Repeat this operation for each step you want to connect or disconnect
Nota :
In manual mode, all steps selected remain connected.
Considering the discharging time of capacitors, the controller allows the reconnection of the same
step after 3 minutes only.
If the selected step number is flashing it means your command has been considered but the
controller is waiting for the appropriate time period.
________________________________________________________________________________
8 – FUNCTIONNING IN MANUAL MODE
to enter the menu page
and press
key to validate