Failure
blink rate
error LED
1
2
3
4
5
6
7
8
Pos: 29 /Technische Dokumentation/Allgemeine Module/#### Seitenumbruch #### @ 0\mod_1426069111812_0.docx @ 891 @ @ 1
01|2016
Possible cause
Failure in the
microprocessor
Undervoltage
Temperature too
high / too low
Overcurrent
triggering
Overvoltage
Shaft blocked
Self-test
Motor error
Remedy
Microprocessor
restarts
Power supply
< 180 V AC
Controller automatic-
ally activates when
the voltage is over
209 V for at least 6
seconds
Temperatur too high
> 100 °C
Temperature too low
< -20 C
Current too high
Internal overcurrent
protection switched
Power supply
> 269 V AC
Load on the shaft too
high or
motor stopped
One or more self-
tests not run
sucessfully
One or more phases
not connected
EN 23