Installation Instructions for the All Pro APC/APCH Combo, and APXH Exit with Remote Capacity
Figure 1
Hole Plug-Remove For
Wall Mount
Figure 2
Remove
Plug To
Mount
Head In
Remove Slot To
These
Mount Head In
Locations
These Locations
CEILING OR END MOUNT INSTALLATION
1. De-energize the circuit at the junction box (J-box) where the
exit sign is to be installed.
2. Place the provided screws in the canopy screw holes. Tabs
inside the holes will prevent the screws from falling out
during installation.
3. Remove the appropriate mounting hole plug on the top
(ceiling mount) or side (end mount) of the frame.
2
2
Mounting Plate
Canopy
Hole Plug-Remove For
Ceiling Mount
Mounting Plate
Canopy
Remove Heads From
Cardboard Retainer
Remove 4 Tabs
To Open Slot
4. Feed the orange, black, and white wires through the canopy
nose.
5. Feed the wires from the J-box through the steel mounting
plate, and then attach the mounting plate to the J-box with
installer provided hardware.
6. Connect the J-box wires to the EXIT power supply wires
using the wire nuts provided. Connect the white wire to
neutral. If using 120V, connect the black wire to the hot lead.
If using 277V, connect the orange wire to the hot lead. Cap
the unused lead. Press the wires into the J-box.
7. Secure the EXIT canopy to the steel mounting plate using
the screws placed in the canopy in step 4.
8. Attach battery leads to PCB.
9. Snap the EXIT stencil onto the frame.
10.Energize AC supply, LED display will come on. LED heads
will illuminate briefly.
SELF POWERED OPERATION
Depress the test switch. The LED display will remain lit and the
charge LED will extinguish when the switched to battery power.
LED heads will illuminate as long as the button is pushed.
Release the test switch. The charge LED will illuminate and the
LED display will operate from the AC supply. The LED heads
will turn off.
MAINTENANCE
None required. Replace the batteries as needed according
to ambient conditions. However, we recommend that the
equipment be tested regularly in accordance with local codes.
NOTE: Servicing of any parts should be performed by qualified
personnel. Only use replacement parts supplied by Eaton's
Lighting business.
CAUTION: This equipment is furnished with a sophisticated low
voltage battery dropout circuit to protect the battery from over
discharge after its useful output has been used. Allow 24 hours
recharge time after installation or power failure for 90 minute
testing.
TROUBLE SHOOTING GUIDE
If LED heads or charge indicator LED does not illuminate, check
the following:
1. Check AC supply – verify that unit has 24 hour AC supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours and
then re-test.
4. If following the above trouble shooting hints does not
solve your problem, contact your local Eaton Lighting
representative for assistance.