Definition Of Analog Signal By Remote Controller - Mitsubishi Electric PAC-IF021B-E Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 103
. Definition of analog signal by remote controller (Required only for ANALOG TEMP. system)
Set following 2 parameters to assign the target temperature value to analog signal figures.
(1) Press
INITIAL SETTING
(2) [DISPLA
Y
]
AD INPUT
HEATING
Press
button
MODE
AD INPUT
Set flow temp. for No.1 and No.2 with
HEATING
AD INPUT
Set flow temp. for No.1 and No.2 with
COOLING
Press
button
ON/OFF
♦ In order to let FTC memorize set parameters
Make sure to press
CIR.WATER
If you press
button
ON/OFF
making any change.
˚C
TEMP.
24
button
for 3 seconds to activate this setting mode.
AD INPUT
COOLING
to switch to the next parameter setting.
to switch
alternately. (The blinking figure can be changed.)
button
before exit from ANALOG SIGNAL ADJUST mode.
before pressing
CIR.WATER
˚C
ON/OFF
[TEMP] buttons (
and
)
[TEMP] buttons (
and
)
button
in ADJUST mode, you can exit from this mode without
FLOW TEMP.
No.2
No.1
.
4mA -------------------------20mA
1V ------------------------------ 5V
0V ----------------------------- 10V
.
ANALOG
SIGNAL

Publicidad

Tabla de contenido
loading

Tabla de contenido