Positioning of combs
After cleaning the recovery unit make sure the combs are positioned correctly, as shown
in fig. 37. Tighten the nuts on the compressor disk "A" respecting the torque setting of
0.6 Nm. If a torque wrench is unavailable, check that there is a fume passage of 1 mm
between the coils.
A
0.6 Nm
60°
60°
60°
fig. 37 - Positioning of combs
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore
operation press the RESET button (detail 8 - fig. 1) for 1 second or use the RESET on
the remote timer control (optional) if installed; if the boiler does not restart it is necessary
to eliminate the fault indicated in the operation LEDs.
Other faults cause temporary shutdowns (marked with the letter "F") which are automat-
ically reset as soon as the value returns within the boiler's normal working range.
48
EN
ATLAS D32 CONDENS K130 UNIT
60°
60°
60°
cod. 3541A624 - Rev. 02 - 03/2015
Table. 6 - List of faults
Fault
Fault
code
A01
Burner block
A02
Flame present signal with burner off
Overtemperature protection activa-
A03
tion
A04
Card parameter fault
Preheater fault (the contact does not
F07
close in 120 seconds)
F09
Card parameter fault
F10
Delivery sensor 1 fault
F11
DHW sensor fault
F12
Card parameter fault
F14
Delivery sensor 2 fault
F16
Card parameter fault
F34
Supply voltage under 170V.
F35
Faulty mains frequency
F37
Incorrect system water pressure
F39
External probe fault
F40
Incorrect system water pressure
A41
Sensor positioning
F42
Heating sensor fault
F47
System water pressure sensor fault
Possible cause
Cure
Pump blocked
Replace
Faulty electric motor
Replace
Faulty oil valve
Replace
No fuel in tank, or water on bottom
Refill with fuel or suck the
water
Oil line feed valves closed
Open
Dirty filters (line-pump-nozzle)
Clean
Pump unprimed
Prime and find the cause
of unpriming
Ignition electrodes dirty or not prop-
Adjust or clean them
erly adjusted
Nozzle clogged, dirty or deformed
Replace
Unsuitable head and shutter adjust-
Adjust
ments
Faulty electrodes or earthed
Replace
Faulty ignition transformer
Replace
Faulty electrode wires or earthed
Replace
Electrode wires deformed by high
Replace and protect
temperature
Incorrect transformer or valve elec-
Check
trical connections
Broken pump-motor joint
Replace
Pump inlet connected to return pipe Correct the connection
Faulty photoresistance
Replace
Dirty photoresistance
Clean the photoresistance
Replace the photoresist-
Photoresistance short circuit
ance
Extraneous light strikes the photore-
Eliminate light source
sistance
Check the correct position-
Heating sensor damaged
ing and operation of the
heating sensor
Check the circulating
No water circulation in the system
pump
Air in the system
Vent the system
Check the card parameter
Wrong card parameter setting
and modify it if necessary
Preheater fault
Check the preheater
Wiring disconnected
Check the wiring
Check the card parameter
Wrong card parameter setting
and modify it if necessary
Sensor damaged
Check the wiring or
Wiring shorted
replace the sensor
Wiring disconnected
Sensor damaged
Check the wiring or
Wiring shorted
replace the sensor
Wiring disconnected
Check the card parameter
Wrong card parameter setting
and modify it if necessary
Sensor damaged
Check the wiring or
Wiring shorted
replace the sensor
Wiring disconnected
Check the card parameter
Wrong card parameter setting
and modify it if necessary
Check the electrical sys-
Electric mains trouble
tem
Check the electrical sys-
Electric mains trouble
tem
Pressure too low
Fill the system
Sensor damaged
Check the sensor
Check the wiring or
Probe damaged or wiring shorted
replace the sensor
Probe disconnected after activating
Reconnect the external
the sliding temperature
probe or disable the sliding
temperature
Check the system
Pressure too high
Check the safety valve
Check the expansion tank
Check the correct position-
Delivery sensor not inserted in
ing and operation of the
boiler shell
heating sensor
Sensor damaged
Replace the sensor
Wiring disconnected
Check the wiring