7.3. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
ON
OFF
SW
1
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
ON
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00
Default
Filter
indicator
11
01
Longer
interval
02
Shorter
00
Enable
01
Disable
Filter
indicator
13
Display
action
only on
02
central
remote
controller
00
Default
Cool air
tem-
30
01
Adjust (1)
perature
trigger
02
Adjust (2)
00
Default
Heat air
01
Adjust (1)
tem-
31
perature
02
Adjust (2)
trigger
03
Adjust (3)
En-13
9373870111-01_IM.indb Sec1:13
9373870111-01_IM.indb Sec1:13
DIP switch "SET4"
SW
SW
SW
2
3
4
Cooling temperature setting range
Standard (18 to 30 °C)
Extension (18 to 32 °C)
Default
Details
○
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
○
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
○
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
○
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
00
Enable
Auto
40
restart
01
Disable
00
Super low
Cool Air
Follow the
Preven-
43
setting on
tion
01
the remote
controller
00
Start/Stop
External
Emergen-
46
01
control
cy stop
Forced
02
stop
00
All
Display
Error re-
47
only on
port target
01
central
remote
controller
Follow the
Fan set-
setting on
ting when
00
the remote
cooling
49
controller
thermostat
OFF
01
Stop
8. TEST RUN
] 1
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using remote controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl ash slowly at the same time.
For details, please refer to the Manual of "IR Receiver Unit" or "Wired Remote Controller".
9. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
] 1
installation is complete, be sure to check the following check items again.
Check items
Has the indoor unit been installed cor-
Vibration, noise, indoor unit may drop
rectly?
Has there been a check for gas leaks
No cooling, No heating
(refrigerant pipes)?
Has heat insulation work been com-
Water leakage
pleted?
Does water drain easily from the
Water leakage
indoor units?
Is the voltage of the power source the
same as that indicated on the label on
No operation, heat or burn damage
the indoor unit?
Are the wires and pipes all connected
No operation, heat or burn damage
completely?
Is the indoor unit earthed (grounded)?
Short circuit
Is the connection cable the specifi ed
No operation, heat or burn damage
thickness?
Are the inlets and outlets free of any
No cooling, No heating
obstacles?
Does start and stop air conditioner
operation by remote controller or
No operation
external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
sdasdsadxxxx
Enable or disable automatic system
○
restart after a power outage.
○
Restrain the cold airfl ow with mak-
ing the airfl ow lower when starting
heating operation. To correspond to
the ventilation, set to 01.
Allow an external controller to start
○
or stop the system, or to perform
an emergency stop.
* If an emergency stop is performed
from an external controller,
all refrigerant systems will be
disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by
a remote controller is restricted.
○
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the wired
remote.
When set to 01, the fan stops when
○
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
Check
If not performed correctly
box