B
B
ATTERY
OX
THE BATTERY BOX IS AN OPTIONAL ACCESSORY.
The Battery Box contains batteries that increase the operating time of the UPS during prolonged black-outs. The number
of batteries contained in it will vary according to the type of UPS to which the Battery Box is to be installed. The utmost
attention must be paid to ensure that the battery voltage of the Battery Box corresponds to that supported by the UPS.
Additional Battery Boxes may be connected in a chain to obtain the desired autonomy time during a power failure.
This series of Battery Box contains two separate strings of batteries, one with a positive voltage and the other with a
negative voltage with respect to the neutral terminal (N).
The basic diagram for the Battery Box is shown here below.
Rated voltage
Weight
W x D x H
IV330 Rev.001 SIEL S.p.A.
Data di emissione: 2011-09-28
(
)
OPTIONAL
BBX 1320 480V
BBX 1320 480V
BB NP T4 3F
240 + 240 Vdc
300 Kg
BBX 1320 480V
BB NP T2 3F
BB NP T8 3F
240 + 240 Vdc
240 + 240 Vdc
390 Kg
400 x 815 x 1320 mm
BBX 1320 480V
BB NP T5 3F
240 + 240 Vdc
395 Kg
400 Kg
Pag. 60 di 252 + FR