Alarm List - Parker Hiross ATT Serie Manual De Uso

Ocultar thumbs Ver también para ATT Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 31
7

Alarm list

Alarm
Display
Code
025-040
WARNING PROBE AD In-
A01
letTemperature
WARNING PROBE Purge Air
A02
Temperature
WARNING PROBE Dewpoint
A03
Meter
WARNING PROBE Heater
A04
Outlet Temperature 1
WARNING PROBE Heater
A05
Outlet Temperature 2
WARNING PROBE Compres-
A06
sor DischargeTemperature
WARNING PROBE Thermal
A07
MassTemperature
WARNING PROBE Capacitive
A08
Level
ALARM FRIDGE High Pres-
A09
sure by pressure switch
ALARM FRIDGE High
A10
Temperature by temperature
switch
WARNING ADSORBER High
A11
AD Inlet Temperature
ALARM FRIDGE Low AD Inlet
A12
Temperature
WARNING ADSORBER High
A13
Electrical Heater Temperature
Column 1
WARNING ADSORBER High
A14
Electrical Heater Temperature
Column 2
WARNING ADSORBER Low
A15
Electrical Heater Temperature
Column 1
English
ATT
ATT
ATT
Reset
060-090
140-340
A
X
X
A
X
X
X
A
X
X
X
A
X
x
X
A
X
X
X
A
Nu
X
A
Nu
X
A
NU
X
A
X
X
A
X
Nu
A,
X
X
se T<13°C(**)
A
X
X
A,
X
X
X
se T<150°C(**)
X
X
X
X
A, T>(setpoint
X
X
X
resistenza – 30
+ 20) (**)
Delay
Defoult conditions to active the alarm
AIN Ad Inlet Temperature
4 s
AIN Purge Air Temperature
3 s
AIN Dewpoint Meter
3 s
AIN Heater Outlet Temperature A PROBE Not Connected Or Faulty
3 s
AIN Heater Outlet Temperature B PROBE Not Connected Or Faulty
3 s
AIN Compressor Discharge Temperature
3 s
AIN Thermal Mass Temperature PROBE Not Connected Or Faulty
3 s
AIN Capacitive Level
3 s
DIN High refrigerant pressure switch Active
Immediate
DIN High Temperature switch Active
Imm.
180s
180s
5s
A, se
T<150°C
(**)
600s
ATT060-090
Stop
Compressor
5s
Stop Dryer
Alarm
relay
Y
N
Active
N
N
Active
N
N
Active
N
N
Active
N
N
Active
Y
N
Active
N
N
Active
N
N
Active
Y
N
Active
Y
N
Active
N
N
Active
Y
N
Active
N
N
Active
N
N
Active
N
N
Active
9 / 14

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Att060Att090

Tabla de contenido