EXTERNAL TEMPERATURE OFFSET FUNCTION
This function allows user to change the selected set point according to the external temperature as
measured by a (duly programmed) K30 transmitter and re-transmitted in digital format (TTL)
to TLK94 controller.
This function relies on 2 parameters, Ad1 and Ad2, to define the extent of the offset at operation
range limits, i.e.:
Ad1 is the value to be added to selected set point when external temperature gets below zero.
Ad2 is the value to be added to selected set point when external temperature gets above zero.
Example
SP = 70 (with external temperature = 0 °C)
Ad1 = +10
Ad2 = -10
If external temperature is +20 °C (limit set for the transmitter) the boiler set point changes as follows:
[SP + (Ad2)] = [70 + (-10)] = 60 °C
If external temperature is -20 °C (limit set for the transmitter) the boiler set point changes as follows:
[SP + (Ad1)] = [70 + (10)] = 80 °C
NOTE:
1) The sum of set point + offset will be limited by SPLL and SPLH parameters
2) When transmitter detects a probe error or is not working or not present, TLK94 will use the local
set point.
Cavo collegamento
Cavo collegamento
Connection cable
TLK94
Da K30 a TLK94
Lato
Lato
Da K30 a TLK94
from K30 to TLK94
side
Baltur
Baltur
TLK 94
TLK 94
Cable-side connector
Cable-side connector
Connettore
Connettore
lato cavi
lato cavi
Rosso
Rosso
Marrone
Marrone
1
1
Connection cable with K30-type transmitter (code CATTLB200--).
Cavo di collegamento con trasmettitore tipo K30 (cod
Cavo di collegamento con trasmettitore tipo K30 (cod
CATTLB200--).
CATTLB200--).
K30
Lato
Lato
side
K30
K30
Connettore
Connettore
lato cavi
lato cavi
Rosso
Rosso
Marrone
Marrone
1
1
ice
ice
The regulator is factory-set with input Pt1000 2 wires, PID regulation for heating. The regulation relays
are K1 and K2. (1, 2)
INITIAL PASSWORD
381
CONNECTION WIRING DIAGRAM
DIG. IN 1
DIG. IN 2
RS485
+12 VDC
4..20
0/1..5 V
PTC
mA
0/2..10 V
Pt
(passive)
1000
INPUT
3 / 16
0006160005_201502
6a
5a
4a
+
NO
3a
A
C
B
2a
NO
+
+
GND
1a
G
C
6b
NC
+
+
5b
G
NO
4b
3b
2b
1b
Pt
TC
100
OUTPUTS
RELAYS:
Out1: 6A-AC1(3A-AC3)/ 250 VAC
Out2,3,4,5: 4A-AC1(2A-AC3)/ 250 VAC
SSR: 12 VDC/20 mA
ANALOG.: 0/4..20mA - 0/2..10V
12a
11a
10a
9a
Out3
8a
7a
Out2
12b
11b
10b
Out1
9b
8b
220V
7b

Hide quick links:

Publicidad

Tabla de contenido
loading

Productos relacionados para baltur LC3

Tabla de contenido