By means of keys "UP" or "DOWN" it is possible to scroll down the settings:
"OPEr"
it allows to access the menu of the operating parameters
"ConF
it allows to access the menu of the setting parameters
"OFF"
it allows to put the regulator in the OFF status
"rEG"
it allows to put the regulator in the automatic status
"tunE"
it allows to activate the Autotuning and Selftuning functions
it allows to put the regulator in the manual status and therefore to set the regulation
"OPLO"
value % by means of keys UP and DOWN
RESTORING THE DEFAULT PARAMETER SETTING
The device allows to reset the parameters to the default factory-set values.
To restore the default values it is necessary to follow the following procedure:
Stop the feed from the device, press key U and feed it again by keeping pressed the key.
After the initial test, "rSEt" will appear on the upper display and "0" on the lower display.
Now it is possible to enter, by using keys UP and DOWN, number 481 and then press key "P" twice.
Once the password is confirmed with key P for the second time the display will show "donE" for about
2 sec, then the device carries out the restoring as for upon ignition and restores all the parameters
bringing them to the default factory-set values.
Once CONF is selected, press key "P" to confirm it.
Now insert, by using the keys UP and DOWN, the password number and then press key "P".
If you insert a wrong password, the device goes back to the previous setting status.
If the password is correct, the display will show the code identifying the first group of parameters ("SP")
and with keys UP and DOWN you can to select the group of parameters that need to be edited.
Once the desired group of parameters has been selected press key P and the code that identifies the
first parameter of the selected group will be displayed.
With keys UP and DOWN it is also possible to select the desired parameter, and by pressing key P
the display will show the code of the parameter and its setting, which can be modified with keys UP
and DOWN.
Once the desired value has been set, press again key P: the new value will be stored and the display
will show again only the symbol of the selected parameter. By pressing keys UP or DOWN it is possible
to select another parameter of the group (if available) and change it as described above.
To select another group of parameters keep pressed key UP and DOWN for about 2 seconds, after
which the display will show again the code of the group of parameters.
Now release the key and with keys UP and DOWN, you can select another group and access its
parameters as described above.
In order to disable the programming mode do not press any key for about 20 seconds, or keep pressed
key UP and DOWN for more than 2 seconds until the programming mode is disabled.
The menu "OPEr" programming mode and programming disabling are the same described for "ConF"
menu with the only difference that to access menu "OPEr" no password is required.